Troubleshooting
Service Diagnosis
101
4.23 CT or Related Abnormality (RXG50K2V1B Only)
Error Code
H8
Method of Error
Detection
A CT or related error is detected by checking the compressor running frequency and CT-
detected input current.
Error Decision
Conditions
The compressor running frequency is more than
A
Hz, and the CT input current is less than
B
A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A
(Hz)
B
(A)
55
0.5