Troubleshooting
SiBE041012_B
106
Service Diagnosis
4.26 Radiation Fin Temperature Rise
Error Code
L4
Method of Error
Detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
compressor on.
Error Decision
Conditions
If the radiation fin temperature with the compressor on is above
A
°C.
The error is cleared when the radiation fin temperature drops below
B
°C.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit
PCB.
A
(°C)
B
(°C)
25/35 class
98
78
RXG50K2V1B
105
99
RXG50K3V1B
85
56