Refrigerant Piping Work

2.

Refrigerant piping.

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. 

2-1. Caution on piping handling.

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

2-2. Selection of copper and heat insulation materials.

• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam

Heat transfer rate: 0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation 

dimensions as below.

3) Use separate thermal insulation for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

Piping union

Flare nut

Spanner

[Tighten]

3/8 inch

1/4 inch

Torque wrench

Flare nut tightening torque

Gas side

32.7-39.9N • m

(330-407kgf • cm)

14.2-17.2N • m

(144-175kgf • cm)

Liquid side

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt 
or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Inter-unit wiring

Liquid pipe

Drain hose

Finishing tape

Gas pipe 

insulation

Liquid pipe 

insulation

Summary of Contents for FTXL25J2V1B

Page 1: ...INSTALLATION MANUAL R410A Split Series Models FTXL25J2V1B FTXL35J2V1B ATXL25J2V1B ATXL35J2V1B DAIKIN...

Page 2: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 3: ...may cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections o...

Page 4: ...ite where remote controller signals are properly received by the indoor unit within 7 metres CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In...

Page 5: ...d push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the centr...

Page 6: ...panel 50mm or more from walls on both sides Air filters Titanium apatite deodorizing filter 2 Air filter Titanium apatite deodorizing filter Filter frame Tab Service lid Opening service lid The servi...

Page 7: ...the wall with screws Recommended mounting plate retention spots and Dimensions Use tape measure as shown Position the end of a tape measure at Keep here the piece cut out from the unit for piping Liqu...

Page 8: ...pes keep the following precautions in mind Abnormal sound may be generated if improper work is conducted 1 Do not strongly press the refrigerant pipes onto the bottom frame 2 Do not strongly press the...

Page 9: ...the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the interconnecting wire ends are to be stripped first bundle wire ends wi...

Page 10: ...to remove the drain hose 2 Reattach the insulation fixing screw on the right as it was Forgetting to attach this may cause water leakages 3 Remove the drain plug on the left side and attach it to the...

Page 11: ...IRCUIT BREAKER AC CN E HA HE HL HN HR MR _A MR _B S U V W X A CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER...

Page 12: ...e 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps inv...

Page 13: ...ct into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the flap 2 Ins...

Page 14: ...rly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous...

Page 15: ...Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide i...

Page 16: ...cessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P377527 2D 2017 02 Copyright 2014 Daikin...

Reviews: