SiUS042113E
Trial Operation
Part 7 Trial Operation and Field Settings
151
Test Items
Test items
Symptom
Indoor and outdoor units are installed securely.
Fall, vibration, noise
No refrigerant gas leaks.
Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain
hose extension are thermally insulated.
Water leakage
Draining line is properly installed.
Water leakage
System is properly grounded.
Electrical leakage
Only specified wires are used for all wiring, and all
wires are connected correctly.
No operation or burn damage
Indoor or outdoor unit’s air inlet or air outlet are
unobstructed.
Incomplete cooling/heating function
Stop valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote controller
commands.
No operation
Attached SSID sticker with release paper (1 pc.) is
given to the user.
Unable to connect to wireless LAN