SiUS04-904
Troubleshooting
140
Service Diagnosis
4.21.2 15/18/24 Class
Remote
Controller
Display
U0
Method of
Malfunction
Detection
Refrigerant shortage detection I :
Refrigerant shortage is detected by checking the CT-detected input current value and the
compressor running frequency.
Refrigerant shortage detection II:
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends to
rise.
Refrigerant shortage detection III:
Refrigerant shortage is detected by checking the difference between air suction and discharge
temperature.
Malfunction
Decision
Conditions
Refrigerant shortage detection I :
Input current <
(A/Hz) x Compressor running frequency V
However, when the status of running frequency > 55 (Hz) is kept on for a certain time.
Note : The values are different from model to model.
If refrigerant shortage error takes place 4 times successively, the system is shut down. The error
counter is reset if this or any other error does not occur during the following 60-minute compressor
running time (total time).
Supposed
Causes
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Discharge pipe thermistor disconnected, or indoor unit or outdoor unit heat exchanger
thermistor disconnected, room or outside air temperature thermistor disconnected
Stop valve closed
Electronic expansion valve defective
1756 / 256
–50
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...