Main Functions
SiUS04-904
30
Function and Control
1.8
INTELLIGENT EYE
This function detects movement in the room by a motion sensor (INTELLIGENT EYE), reducing
capacity when the room is empty in order to save electricity.
Processing
1. Detection method by INTELLIGENT EYE
This sensor detects human motion by receiving infrared rays and displays the pulse wave
output.
A microcomputer in the indoor unit carries out a sampling every 20 msec. and if it detects 10
cycles of the wave in one second in total (corresponding to 20msec. 10 = 200msec.), it
determines that there is movement in the room as the motion signal is ON.
2. The motions (for example: in cooling)
When a microcomputer does not have a signal from the sensor in 20 minutes, it detects that
nobody is in the room and operates the unit at a temperature shifted
3.6°F(2°C) from the set
temperature. (COOL :
3.6°F(2°C) higher, DRY:
1.8°F(1°C) higher, AUTO : according to the
operation mode at that time.)
1 In case of FAN mode, the fan speed reduces by 50 rpm.
If the sensor detects the outputs 10 times/sec.
or more, it judges humans exist.
1sec
sampling (20 msec)
High
Low
ON
OFF
Sensor output
(Human motion)
Human detection
signal
(R2821)
ON
OFF
RESET.
C/O Set temp. +
Δ
3.6˚F
H/P Set temp. -
Δ
3.6˚F
Human detection
signal
20 min.
20 min.
within 20
minutes.
40 min.
MaxHz
Mi nHz
0Hz
Compressor
speed
The lower limit by detecting
human.
(Prohibition of thermostat-off)
ON
OFF
ON
OFF
Operation
OFF
Fan speed (
1)
Set speed - 50 rpm
Set speed
Set speed
in case of
thermostat-off
Frequency at set temp. +
Δ
3.6˚F
Set temp.
(R0272)
Remote controller
INTELLIGENT EYE
button
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...