Control Specification (15/18/24 Class)
SiUS04-904
60
Function and Control
4.13.3 Refrigerant Shortage Control
Outline
If a power consumption is below the specified value in which the frequency is higher than the
specified frequency, it must be regarded as refrigerant shortage.
In addition to such conventional function, if the discharge pipe temperature is higher than the target
discharge pipe temperature, and the electronic expansion valve is fully open (450 pulses) more
than the specified time, it is considered as refrigerant shortage.
With the conventional function, a power consumption is low comparing with that in the normal
operation when refrigerant is insufficient, and refrigerant shortage is detected by checking a power
consumption.
When operating with refrigerant shortage, although the rise of discharge pipe temperature is great
and the electronic expansion valve is open, it is presumed as refrigerant shortage if the discharge
pipe temperature is higher than the target discharge pipe temperature.
Refer to “Refrigerant Shortage” on page 138 for detail.
Detail
Judgment by Input Current
When an output frequency is exceeds 55 Hz and the input current is less than specified value, the
adjustment is made for refrigerant shortage.
Judgment by Discharge Pipe Temperature
When discharge pipe temperature is
36°F higher than target value and the electronic expansion
value opening is 450 plus (max.), the adjustment is made for refrigerant shortage.
Frequency
Power consumption
Refrigerant shortage zone
55 Hz
(R2834)
Refrigerant shortage
zone
(R1391)
Summary of Contents for FTXS09HVJU
Page 1: ...SiUS04 904 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type H Series...
Page 9: ...Safety Considerations SiUS04 904 viii Safety Considerations...
Page 10: ...SiUS04 904 List of Functions 1 Part 1 List of Functions 1 Functions 2...
Page 72: ...Control Specification 15 18 24 Class SiUS04 904 62 Function and Control...
Page 77: ...FTXS09 12HVJU SiUS04 904 66 Operation Manual...
Page 78: ...SiUS04 904 FTXS09 12HVJU Operation Manual 67...
Page 83: ...FTXS09 12HVJU SiUS04 904 72 Operation Manual is no longer displayed on the LCD...
Page 84: ...SiUS04 904 FTXS09 12HVJU Operation Manual 73 is no longer displayed on the LCD...
Page 85: ...FTXS09 12HVJU SiUS04 904 74 Operation Manual...
Page 86: ...SiUS04 904 FTXS09 12HVJU Operation Manual 75...
Page 87: ...FTXS09 12HVJU SiUS04 904 76 Operation Manual 3P232717 1C...
Page 90: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 79 is no longer displayed on the LCD...
Page 91: ...FTXS15 18 24HVJU SiUS04 904 80 Operation Manual...
Page 94: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 83 is no longer displayed on the LCD...
Page 95: ...FTXS15 18 24HVJU SiUS04 904 84 Operation Manual Do not hit or forcefully push the operation...
Page 96: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 85 is no longer displayed on the LCD...
Page 97: ...FTXS15 18 24HVJU SiUS04 904 86 Operation Manual is no longer displayed on the LCD...
Page 98: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 87 is no longer displayed on the LCD...
Page 99: ...FTXS15 18 24HVJU SiUS04 904 88 Operation Manual...
Page 100: ...SiUS04 904 FTXS15 18 24HVJU Operation Manual 89...
Page 101: ...FTXS15 18 24HVJU SiUS04 904 90 Operation Manual 3P232717 2C...