ESIE17-19C
|
Part 1. Introduction
1.3. General operation
Page 14
19/08/19
|
Version 1.1
Optimized Heating 4
1.3. General operation
•
These split units are used for comfort heating/cooling and are equipped with an inverter.
•
The rotation speed rps (= rotation per second) of the inverter driven compressor, modulated by the inverter, can be varied
according the required capacity in the room.
•
The compressor capacity step is changed in order to reach target compression ratio. The target compression ratio is calculated
from deviation between actual and target condensation and evaporation temperature.
• Tc
(condensing
temperature) is used in heating mode.
•
Te (evaporation temperature) is used if any indoor unit operates in cooling mode.
•
The evaporating temperature in the heat exchanger is controlled by the electronic expansion valve.
•
When indoor unit is selecting heating mode, discharge gas is supplied by the outdoor unit to the indoor unit.
•
When indoor unit is selecting cooling mode, liquid refrigerant is supplied by the outdoor unit to the indoor unit.
1. Compressor
4. Outdoor heat exchanger
2. Indoor heat exchanger
5. 4-way valve
3. Expansion valve
6. Stop valves