background image

DAIKIN ROOM AIR CONDITIONER

INSTALLATION MANUAL

R32 Split Series

English

De

ut

sch

Fra

n

ça

is

Русский

Dansk

Sven

ska

Norsk

Su

om

i

Polski

Models

FTXTP25K3V1B
FTXTP35K3V1B
ATXTP25K3V1B
ATXTP35K3V1B

3PEN482320-6B.book  Page 1  Wednesday, July 12, 2017  2:30 PM

Summary of Contents for FTXTP25K3V1B

Page 1: ...IONER INSTALLATION MANUAL R32 Split Series English Deutsch Français Русский Dansk Svenska Norsk Suomi Polski Models FTXTP25K3V1B FTXTP35K3V1B ATXTP25K3V1B ATXTP35K3V1B 3PEN482320 6B book Page 1 Wednesday July 12 2017 2 30 PM ...

Page 2: ...te da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 1...

Page 3: ... up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If the supply cord is damaged it must be replaced by the manufacturer a service agent or similarly qualified persons in...

Page 4: ...ainage and insulate piping to prevent condensation Improper drain piping may result in indoor water leakage and property damage Tighten the flare nut according to the specified method such as with a torque wrench If the flare nut is too tight it may crack after prolonged use causing refrigerant leakage This appliance is intended to be used by expert or trained users in shops in light industry and ...

Page 5: ... warm air is circulated throughout the room 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote controller range 8 the unit is at least 1m away from any television or radio set unit may cause interference with the picture or sound 9 install at the recommended height 1 8m 10 no laundry equipment is located 11 the appliance s...

Page 6: ...s under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and then mount the front panel 3 How to set the different addresses When 2 indoor units are installed in one room the 2 wireless remote controllers can be set for d...

Page 7: ...al wiring cover as it was and pull the harness around as shown in the figure Removal method of metal plate electrical wiring covers 1 Remove the front grille 2 Remove the electrical wiring box 1 screw 3 Raise the upper part of the metal plate electrical wiring cover pull the part frontward and remove the 3 tabs The appearance of the box may differ for classes 25 35 HA connector S21 Lay the HA cord...

Page 8: ...oor unit Push up the marked area at the lower part of the front grille to release the hooks If it is difficult to release remove the front grille 30mm or more from ceiling Front panel 50mm or more from walls on both sides Air filters A A Titanium apatite deodorizing filter 2 B The service lid is removable Appearance of indoor units may differ from some models Titanium apatite deodorizing filter Re...

Page 9: ...ll cover in the feed through hole to prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent water leakage 1 Bore a feed through hole of 65mm in the wall so it has a down slope toward the outside 2 Insert a wall pipe into the hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping ca...

Page 10: ...ace 2 After cutting off the pipe port cover perform filing Remove the burrs along the cut section using a half round needle file CAUTION If the pipe port cover is cut off using nippers the front grille will be damaged Please do not use nippers Wear gloves during the pipe port cover removal 3 1 Right side right back or right bottom piping 1 Attach the drain hose to the underside of the refrigerant ...

Page 11: ... hose Replacing onto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing screw Forgetting to tighten this may cause water leakages Mounting plate Wire guide When stripping off the ends of inter unit wire in advance cover ...

Page 12: ...il it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with indoor unit fixing screws M4 12L 3 3 Wall embedded piping Follow the instructions given under left side left back or left bottom piping 1 Insert the drain hose to this depth so it won t be pulled out of the drain pipe Drain hose Caulk this hole with putty or caulking material Bind with adhesive vinyl t...

Page 13: ...L HN HR MR _A MR _B S U V W X A K R_ CONNECTION CONNECTOR Q L OVERLOAD PROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT LAMP LIGHT EMITTINGDIODE S NPL PRESSURE...

Page 14: ...edded drain piping is required use appropriate parts that match the hose front end Figure of hose front end 4 When extending the drain hose use a commercially available extension hose with an inner diameter of 16mm Be sure to thermally insulate the indoor section of the extension hose 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the...

Page 15: ...a dryer to this R32 unit in order to guarantee its lifetime The drying material may dissolve and damage the system Protect or enclose the refrigerant tubing to avoid mechanical damage Incomplete flaring may cause refrigerant gas leakage Installing Place the wireless adapter against the hooks 1 Lock the adapter by pressing it down 2 Removing the reverse process of installing 1 2 A A Cut exactly at ...

Page 16: ...110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side O D 9 5mm O D 6 4mm Minimum bend radius 30mm or more Thickness 0 8mm C1220T O Thickness 0 5mm Gas pipe thermal insulation Liquid ...

Page 17: ...s To stop the operation press Some of the functions cannot be used in the trial operation mode The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore ...

Page 18: ...3PEN482320 6B book Page 1 Wednesday July 12 2017 2 30 PM ...

Page 19: ...3PEN482320 6B book Page 2 Wednesday July 12 2017 2 30 PM ...