90
Engineering & Physical Data
Engineering Data - Chilled Water Fan Coil Unit
MODEL
FWKE11E
HIGH
MEDIUM
LOW
QUIET
NOMINAL COOLING CAPACITY
Btu/h
40100
33100
26800
21000
W
11750
9700
7850
6150
NOMINAL SENSIBLE COOLING CAPACITY
Btu/h
28600
23800
18900
14600
W
8370
6970
5540
4270
NOMINAL HEATING CAPACITY
(ENTERING WATER TEMP. = 50°C)
Btu/h
46700
39100
31600
24100
W
13700
11450
9250
7050
NOMINAL TOTAL INPUT POWER
W
120
83
39
23
NOMINAL RUNNING CURRENT
A
1.23
0.92
0.49
0.32
POWER SOURCE
V/Ph/Hz
208-230 / 1 / 60
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER ( UP & DOWN)
OPERATION
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW
CFM
1060
870
680
510
NOMINAL WATER FLOW RATE
USGPM
9.00
7.43
6.01
4.71
litres/min
34.06
28.12
22.76
17.83
HEAD LOSS (COOLING)
kPa
41
30
22
15
HEAD LOSS (HEATING) : 50°C
kPa
37
26
20
12
MAX. WORKING PRESSURE
kPa
1608
SURFACE AIR VELOCITY
m/s
0.83
0.71
0.57
0.45
SOUND PRESSURE LEVEL
dBA
51
46
41
34
UNIT DIMENSION - (WITH PANEL)
H X W X D
mm
300 X 820 X 820 ( 375 X 990 X 990)
PACKING DIMENSION - (PANEL)
H X W X D
mm
376 X 916 X 916 ( 125 X 1020 X 1020)
UNIT WEIGHT (UNIT + PANEL)
kg
32 + 4
CONDENSATE DRAIN SIZE
mm
19.05
PIPE CONNECTION
mm
19.05 BSP FEMALE THREAD ADAPTOR
FAN
TYPE
TURBO FAN
DRIVE
DIRECT
FAN SPEED
RPM
750
630
510
400
FAN MOTOR
TYPE
BRUSHLESS DIRECT CURRENT
INDEX OF PROTECTION (IP)
IP20
INSULATION GRADE
E
RATED INPUT POWER
W
120
83
39
23
RATED RUNNING CURRENT
A
1.23
0.92
0.49
0.32
STARTING CURRENT
A
2.2
MOTOR OUTPUT
W
100
POLES
8
COIL
TUBE
MATERIAL
COPPER
DIAMETER
mm
7.00
FIN
MATERIAL
ALUMINIUM
FACE AREA
m
2
0.46
ROW
3
WATER VOLUME
litre
2.35
AIR QUALITY FILTER
TYPE
WASHABLE SARANET FILTER
QUANTITY
pc
1
CASING
COLOUR
LIGHT GREY
NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E(H) MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E(H) MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
MODE
COOLING
HEATING
ENTERING AIR TEMPERATURE
27°C DB / 19°C WB
20°C DB
ENTERING WATER TEMPERATURE
7°C
50°C (2 Pipes System)
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE
12°C
60°C (4 Pipes System)
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Summary of Contents for FUD Series
Page 2: ......
Page 4: ...Table of Contents ii...
Page 71: ...67 Fan Performance Chart...
Page 76: ...72 Fan Performance Chart...
Page 77: ...73 Fan Performance Chart...
Page 78: ...74 Fan Performance Chart...
Page 79: ...75 Fan Performance Chart...
Page 80: ...76 Fan Performance Chart...
Page 81: ...77 Fan Performance Chart...
Page 82: ...78 Fan Performance Chart...
Page 88: ...84 Fan Performance Chart...
Page 125: ...121 Wiring Diagrams Model FWC08 10 12G MSP Model FWC02 03 04 06 08 12G EC LSP MSP...
Page 126: ...122 Wiring Diagrams Model FUD20B Model FUD25B...
Page 127: ...123 Wiring Diagrams Model FUD30B...
Page 131: ......