5 Installation

Installation manual

20

FWE03~11D

Fan coil units

3P443944-5P – 2021.12

h

5.3

Connecting the electrical wiring

5.3.1

About connecting the electrical wiring

Typical workflow

Connecting  the  electrical  wiring  typically  consists  of  the  following
stages:

1

Making  sure  the  power  supply  system  complies  with  the
electrical specifications of the units.

2

Connecting the electrical wiring to the fan coil unit.

3

Changing the electrical wiring direction (if applicable).

5.3.2

Guidelines when connecting the electrical
wiring

When connecting wires of the same gauge, connect them according
to the figure below.

Observe  the  notes  mentioned  below  when  connecting  the  electrical
wiring.

▪ Do  NOT  connect  wires  of  different  gauge  to  the  same  power

supply  terminal.  Looseness  in  the  connection  may  cause
overheating.

▪ Do  NOT  connect  wires  of  different  gauge  to  the  same  grounding

terminal.  Looseness  in  the  connection  may  deteriorate  the
protection.

▪ Use  the  specified  electric  wire  (refer  to 

"Specifications  for  field

wiring"

  [

4

  9]).  Connect  the  wire  securely  to  the  terminal.  Use  the

appropriate tightening torque (N•m).

▪ Power supply terminal block tightening torque: 1.44~1.88 N•m.

▪ Keep  the  wiring  neat  so  that  wires  do  NOT  obstruct  other

equipment or force the terminal cover to pop open. Make sure the
cover  closes  tight.  Incomplete  connections  could  result  in
overheating, and in the worst case, electrical shock or fire.

5.3.3

To connect the electrical wiring to the fan
coil unit

Refer to the wiring diagram label on the terminal cover.

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located on the terminal cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the terminal cover.

1

Remove the terminal cover from the unit.

2

Insert the field wiring through the terminal cover rubber (c).

c

3

Connect  the  power  supply  and  remote  controller  cables  to  the
terminal strip.

4

Reattach the terminal cover to the unit.

5

Fix the power supply cable with the cable holder.

Summary of Contents for FWE03D Series

Page 1: ...Installation manual Fan coil units English Installation manual Fan coil units FWE03D FWE04D FWE05D FWE06D FWE07D FWE08D FWE10D FWE11D ...

Page 2: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 3: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 4: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 5: ...or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of Fan coil unit installation manual Installation instructions Format Paper in the box of the fan coil unit Latest revisions of the supplied documentation may be available on the regional Daikin website ...

Page 6: ...eck if the installation location can support the unit s weight Poor installation is hazardous It can also cause vibrations or unusual operating noise Provide sufficient service space Do NOT install the unit so that it is in contact with a ceiling or a wall as this may cause vibrations DANGER RISK OF ELECTROCUTION Do NOT operate the fan coil units with wet hands An electrical shock may result DANGE...

Page 7: ...e consult with your dealer to ensure that the external static pressure of the unit is not exceeded INFORMATION The sound pressure level is less than 70 dBA CAUTION Do not use suspension bolts in case of vertical installation Vertical installation must be performed with the vertical installation kit ESFH01D5 ESFH02D5 ESFH03D5 INFORMATION The spacing between ceiling and unit should be 10 mm and the ...

Page 8: ...he unit must be installed 2 5 m from the floor where the unit is hanging in the ceiling 150 mm High floor standing type 10 mm Floor standing type Vertical filter maintenance space should be considered as indicated 150 10 mm Wall mounted type bottom suction 10 150 mm Wall mounted type front suction 10 10 mm ...

Page 9: ... or telephone earth Incomplete earthing may cause electrical shock Make sure to install the required fuses or circuit breakers Make sure to install an earth leakage protector Failure to do so may cause electrical shock or fire NOTICE The equipment described in this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to ...

Page 10: ...r bracket to the suspension bolt Fix the unit securely a b c d a Nut field supply b Washer field supply c Hanger bracket d Double nut field supply 4 Adjust the unit to the correct position for installation 1 100 5 Check if the unit is horizontally levelled Do not install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water ...

Page 11: ...ers with a water level a or a water filled plastic tube b b a Floor standing type ESFH01D5 In case of floor standing installation please follow the instruction as shown below 1 Remove the air filter 2 Remove the service cover c and air filter a from the unit a c 3 Insert the rubber support b included in the option kit in the free area between the side plate and the bottom flanges 4 Reattach the re...

Page 12: ... it to the floor using screws f in the installation leg holes f d f Screw field supply 9 Adjust the unit to the correct position for installing 1 100 10 Check if the unit is horizontally levelled Do NOT install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water to drip Check if the unit is levelled at all four corners wit...

Page 13: ...om or front suction in the wall mounted type Please follow the instruction in case of wall mounting installation as shown below 1 Drill the holes on the wall according to the dimensions as shown on the table below a b c Model a mm b mm c mm FWE03 05D 485 50 710 FWE06D 910 FWE07 11D 1110 2 Mount the wall hangers on the wall with using the dowels a and screws b d 10 mm a ...

Page 14: ...cause the unit to malfunction CAUTION Valves should always be used to control the water circulation in the unit The valve should be of the NC normally closed type so that the valves are closed when the unit is not operating This will prevent condensate water from being produced 5 2 1 To connect the water piping 1 Connect the water inlet and outlet connections of the fan coil unit to the water pipi...

Page 15: ...ditional filling with water afterwards may be required To purge the system use the special function as described in 6 Commissioning 423 NOTICE Make sure water quality complies with EU directive 2020 2184 5 2 3 Installation of the valve kits NOTICE Make the wiring according to the wiring diagram of the remote controller INFORMATION Below graphics show 4 pipe models 2 pipe models are connected in th...

Page 16: ...a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the main pipes of the valve body are DN20 Since no connection is made to the water outlet lines water out threads are 3 4ʺ female BSP ...

Page 17: ...se The difference should be taken into account when preparing the installation area 5 mm a b 5 mm a b Model Option kit Kvs value m3 h diverter mixing Max operation pressure PN bar Actuator power supply 2 pipe 3 way E3V2VN02V3WA 2 8 2 5 16 1 Ph 230 V 50 60 Hz NC Normally closed 4 pipe 3 way E3V4VN02V3WA 1 Wrap teflon tape field supply on the end of the water pipes a and connect it to the water inle...

Page 18: ...2 a 2 Connect the 3 way valve body b to the water pipes a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the valve body are DN20 ...

Page 19: ...V3DA E4V4PN10V3DA 1 1 Wrap teflon tape field supply on the end of the nipple c and water pipe d then connect it to the water inlet and outler line Then connect the connection pipe a by placing a gasket b between it and nipple c d a b c 2 Connect the proportional valve body e by placing the gasket b in between b e 3 Connect the actuator f to the valve body f 4 Wrap the thermal insulation g in the k...

Page 20: ...ss in the connection may deteriorate the protection Use the specified electric wire refer to Specifications for field wiring 49 Connect the wire securely to the terminal Use the appropriate tightening torque N m Power supply terminal block tightening torque 1 44 1 88 N m Keep the wiring neat so that wires do NOT obstruct other equipment or force the terminal cover to pop open Make sure the cover c...

Page 21: ...e side in the field NOTICE When attaching the terminal cover make sure not to pinch any wires 1 Remove the terminal cover terminal cable holder earth wire and fan motor cables a Terminal cover b Wiring diagram label c Power supply cable d Terminal strip e Earth wire f Cable holder 2 Release the fan motor cable from the cable holders a a Fan motor cable 3 Change the direction of the fan motor cable...

Page 22: ... t o t h e n a m e p l a t e L N C 1 Q 1 M M G R N Y L W F 1 U X 1 M 1 5 G R N R E D O R G B R N Y L W B L U G R E E N R E D O R A N G E B R O W N Y E L L O W B L U E N O T E G R N R E D O R G B R N Y L W B L U C 1 G R N Y L W F A N S P E E D S W I T C H X 1 M 2 1 3 4 5 L N L N F 1 U G R N Y L W G R N Y L W M 1 Q 1 M 6 Connect the power supply and remote controller cables to the terminal 7 Attach ...

Page 23: ...rth wires have been connected properly and that the earth terminals are tightened Fuses circuit breakers or protection devices Check that the fuses circuit breakers or the locally installed protection devices are of the size and type specified in 4 4 Preparing electrical wiring 49 Be sure that neither a fuse nor a protection device has been bypassed Internal wiring Visually check the electrical co...

Page 24: ...1 Switch off the power supply 2 The air filter can be installed in 1 of 2 locations on this product side and bottom Remove the filter by sliding as shown below Horizontal installation Remove the filter by sliding min 200 mm Vertical installation Push the tabs at the filter and pull it back min 70 mm ...

Page 25: ...il units 3P443944 5P 2021 12 High floor standing Pull the filter and remove from the unit 3 Use a vacuum cleaner or wash air filter with water When the air filter is very dirty use a soft brush and neutral detergent 4 Set the air filter back to its original position ...

Page 26: ...instruction list Materials Item Electrical part fan motor capacitor 1 Aluminium fin copper tube galvanized steel plate brass 10 Plastic 2 18 8 22 27 Plastic metal 3 17 24 Plastic frame plastic net 4 Galvanized steel 5 9 13 14 16 20 23 25 26 Galvanized steel plastic foam 6 7 11 12 15 19 Plastic foam 21 9 Technical data A subset of the latest technical data is available on the regional Daikin websit...

Page 27: ... 505 56 42 A B C D mm Units mm A B C D FWE03 05D 719 757 799 909 FWE06D 919 957 999 1109 FWE07 11D 1119 1157 1199 1309 Vertical outlook High floor standing type 136 220 711 561 501 418 404 79 129 112 175 206a mm a In case of high floor standing kit ESFH03D5 usage Floor standing outlook ...

Page 28: ...747 909 FWE06 919 957 947 1109 FWE07 11D 1119 1157 1147 1309 Additional drain pan ESFD01D6 CAUTION Make sure to attach the drain socket rubber after installing the additional drain pan Otherwise condensation on the main unit or water pipes air filter dirt or drain blockage may cause dripping resulting in fouling or failure of the object concerned Horizontal installation b c a a Additional drain pa...

Page 29: ...9 Technical data Installation manual 29 FWE03 11D Fan coil units 3P443944 5P 2021 12 Vertical installation c b a a Additional drain pan b Drain socket rubber c Drain socket ...

Page 30: ... 9 3 Wiring diagram On terminal English Translation Connection X1M Main terminal Field supply Protective earth Earth Field wire Fan motor cable WHT White GRN Green RED Red ORG Orange BRN Brown YLW Yellow BLU Blue GRN YLW Green yellow C1 Capacitor F1U Fuse X1M Terminal strip M Fan motor ...

Page 31: ......

Page 32: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P443944 5P 2021 12 Copyright 2019 Daikin Verantwortung für Energie und Umwelt ...

Reviews: