5 Installation

Installation manual

9

FWE03~11D
Fan coil units
3P443944-5P – 2021.12

4.3

Preparing water piping

The  unit  is  equipped  with  a  water  inlet  and  water  outlet  for
connection to the water circuit. The water circuit must be provided by
an installer and must comply with the applicable legislation.

Before performing the water piping work, check the following points:

▪ The maximum water pressure is 1.6 MPa.

▪ The minimum water temperature is 5°C.

▪ The maximum water temperature is 90°C.

▪ Be sure to install components in the field piping that can withstand

the water pressure and temperature.

▪ Provide  adequate  safeguards  in  the  water  circuit  to  ensure  that

the  water  pressure  will  never  exceed  the  maximum  allowable
working pressure.

▪ Provide a proper drain for the pressure relief valve (if installed) to

avoid any water from coming into contact with electrical parts.

▪ Provide shut-off valves at the unit so that normal servicing can be

accomplished without draining the system.

▪ Provide  drain  taps  at  all  low  points  of  the  system  to  permit

complete  draining  of  the  circuit  during  maintenance  or  service  to
the unit.

▪ Provide  air  purge  valves  at  all  high  points  of  the  system.  The

valves  shall  be  located  at  points  which  are  easily  accessible  for
servicing.

NOTICE

The  unit  is  ONLY  to  be  used  in  a  closed  water  system.
Application  in  an  open  water  circuit  can  lead  to  excessive
corrosion of the water piping.

4.4

Preparing electrical wiring

4.4.1

About preparing the electrical wiring

WARNING

▪ ONLY use copper wires.

▪ Make sure the field wiring complies with the applicable

legislation.

▪ All field wiring MUST be performed in accordance with

the wiring diagram supplied with the product.

▪ NEVER  squeeze  bundled  cables  and  make  sure  they

do  NOT  come  into  contact  with  the  piping  and  sharp
edges. Make sure no external pressure is applied to the
terminal connections.

▪ Make sure to install earth wiring. Do NOT earth the unit

to  a  utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Make  sure  to  install  the  required  fuses  or  circuit

breakers.

▪ Make sure to install an earth leakage protector. Failure

to do so may cause electrical shock or fire.

NOTICE

The  equipment  described  in  this  manual  may  cause
electronic  noise  generated  from  radio-frequency  energy.
The  equipment  complies  to  specifications  that  are
designed  to  provide  reasonable  protection  against  such
interference.  However,  there  is  no  guarantee  that
interference will not occur in a particular installation.

It  is  therefore  recommended  to  install  the  equipment  and
electric  wires  in  such  a  way  that  they  keep  a  proper
distance from stereo equipment, personal computers, etc.

WARNING

All  field  wiring  and  components  MUST  be  installed  by  a
licensed  electrician  and  MUST  comply  with  the  applicable
legislation.

DANGER: RISK OF ELECTROCUTION

WARNING

A  main  switch  or  other  means  for  disconnection,  having  a
contact  separation  in  all  poles,  MUST  be  incorporated  in
the  fixed  wiring  in  accordance  with  the  applicable
legislation.

Electrical characteristics

FWE-D

Phase

1 Ph

Frequency

50 Hz

Voltage range

220~240 V

Voltage tolerance

±10%

Maximum running current

0.46 A

Overcurrent fuse

5 A

Earth leakage circuit breaker

Must comply with applicable

legislation

Specifications for field wiring

Wire

Size (mm²)

Length

Power supply
wiring

H05VV-U3G

(a)(b)

According to the
applicable
legislation ≤4.0

Remote
controller and
unit
transmission
wiring

Sheathed wire 2
conductors

(c)

0.75~1.25

≤500 m

(d)

(a)

Only in case of protected pipes. Use H07RN-F in case of no
protection.

(b)

Run electrical wiring through a conduit to protect against external
forces.

(c)

Use double insulation wire for remote controller (sheath thickness
≥1 mm) or run wires through a wall or conduit so that the user
cannot come in contact with them.

(d)

The length shall be the total extended length in a system with
group control.

5

Installation

5.1

Mounting the fan coil unit

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.  Make  sure  that  the  tightening  torque  is  3  N•m  for  all
screws.

Summary of Contents for FWE03D Series

Page 1: ...Installation manual Fan coil units English Installation manual Fan coil units FWE03D FWE04D FWE05D FWE06D FWE07D FWE08D FWE10D FWE11D ...

Page 2: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 3: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 4: ...u z našimi navodili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja li...

Page 5: ...or trained users in shops in light industry and on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of Fan coil unit installation manual Installation instructions Format Paper in the box of the fan coil unit Latest revisions of the supplied documentation may be available on the regional Daikin website ...

Page 6: ...eck if the installation location can support the unit s weight Poor installation is hazardous It can also cause vibrations or unusual operating noise Provide sufficient service space Do NOT install the unit so that it is in contact with a ceiling or a wall as this may cause vibrations DANGER RISK OF ELECTROCUTION Do NOT operate the fan coil units with wet hands An electrical shock may result DANGE...

Page 7: ...e consult with your dealer to ensure that the external static pressure of the unit is not exceeded INFORMATION The sound pressure level is less than 70 dBA CAUTION Do not use suspension bolts in case of vertical installation Vertical installation must be performed with the vertical installation kit ESFH01D5 ESFH02D5 ESFH03D5 INFORMATION The spacing between ceiling and unit should be 10 mm and the ...

Page 8: ...he unit must be installed 2 5 m from the floor where the unit is hanging in the ceiling 150 mm High floor standing type 10 mm Floor standing type Vertical filter maintenance space should be considered as indicated 150 10 mm Wall mounted type bottom suction 10 150 mm Wall mounted type front suction 10 10 mm ...

Page 9: ... or telephone earth Incomplete earthing may cause electrical shock Make sure to install the required fuses or circuit breakers Make sure to install an earth leakage protector Failure to do so may cause electrical shock or fire NOTICE The equipment described in this manual may cause electronic noise generated from radio frequency energy The equipment complies to specifications that are designed to ...

Page 10: ...r bracket to the suspension bolt Fix the unit securely a b c d a Nut field supply b Washer field supply c Hanger bracket d Double nut field supply 4 Adjust the unit to the correct position for installation 1 100 5 Check if the unit is horizontally levelled Do not install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water ...

Page 11: ...ers with a water level a or a water filled plastic tube b b a Floor standing type ESFH01D5 In case of floor standing installation please follow the instruction as shown below 1 Remove the air filter 2 Remove the service cover c and air filter a from the unit a c 3 Insert the rubber support b included in the option kit in the free area between the side plate and the bottom flanges 4 Reattach the re...

Page 12: ... it to the floor using screws f in the installation leg holes f d f Screw field supply 9 Adjust the unit to the correct position for installing 1 100 10 Check if the unit is horizontally levelled Do NOT install the unit tilted If the unit is tilted against the direction of the condensate flow drain piping side raised it will cause water to drip Check if the unit is levelled at all four corners wit...

Page 13: ...om or front suction in the wall mounted type Please follow the instruction in case of wall mounting installation as shown below 1 Drill the holes on the wall according to the dimensions as shown on the table below a b c Model a mm b mm c mm FWE03 05D 485 50 710 FWE06D 910 FWE07 11D 1110 2 Mount the wall hangers on the wall with using the dowels a and screws b d 10 mm a ...

Page 14: ...cause the unit to malfunction CAUTION Valves should always be used to control the water circulation in the unit The valve should be of the NC normally closed type so that the valves are closed when the unit is not operating This will prevent condensate water from being produced 5 2 1 To connect the water piping 1 Connect the water inlet and outlet connections of the fan coil unit to the water pipi...

Page 15: ...ditional filling with water afterwards may be required To purge the system use the special function as described in 6 Commissioning 423 NOTICE Make sure water quality complies with EU directive 2020 2184 5 2 3 Installation of the valve kits NOTICE Make the wiring according to the wiring diagram of the remote controller INFORMATION Below graphics show 4 pipe models 2 pipe models are connected in th...

Page 16: ...a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the main pipes of the valve body are DN20 Since no connection is made to the water outlet lines water out threads are 3 4ʺ female BSP ...

Page 17: ...se The difference should be taken into account when preparing the installation area 5 mm a b 5 mm a b Model Option kit Kvs value m3 h diverter mixing Max operation pressure PN bar Actuator power supply 2 pipe 3 way E3V2VN02V3WA 2 8 2 5 16 1 Ph 230 V 50 60 Hz NC Normally closed 4 pipe 3 way E3V4VN02V3WA 1 Wrap teflon tape field supply on the end of the water pipes a and connect it to the water inle...

Page 18: ...2 a 2 Connect the 3 way valve body b to the water pipes a b 3 Connect the actuator c to the valve body c 4 Wrap the thermal insulation d in the kit to prevent condensation and heat loss d 5 The kit is ready for main pipes connection The threads e connected to the valve body are DN20 ...

Page 19: ...V3DA E4V4PN10V3DA 1 1 Wrap teflon tape field supply on the end of the nipple c and water pipe d then connect it to the water inlet and outler line Then connect the connection pipe a by placing a gasket b between it and nipple c d a b c 2 Connect the proportional valve body e by placing the gasket b in between b e 3 Connect the actuator f to the valve body f 4 Wrap the thermal insulation g in the k...

Page 20: ...ss in the connection may deteriorate the protection Use the specified electric wire refer to Specifications for field wiring 49 Connect the wire securely to the terminal Use the appropriate tightening torque N m Power supply terminal block tightening torque 1 44 1 88 N m Keep the wiring neat so that wires do NOT obstruct other equipment or force the terminal cover to pop open Make sure the cover c...

Page 21: ...e side in the field NOTICE When attaching the terminal cover make sure not to pinch any wires 1 Remove the terminal cover terminal cable holder earth wire and fan motor cables a Terminal cover b Wiring diagram label c Power supply cable d Terminal strip e Earth wire f Cable holder 2 Release the fan motor cable from the cable holders a a Fan motor cable 3 Change the direction of the fan motor cable...

Page 22: ... t o t h e n a m e p l a t e L N C 1 Q 1 M M G R N Y L W F 1 U X 1 M 1 5 G R N R E D O R G B R N Y L W B L U G R E E N R E D O R A N G E B R O W N Y E L L O W B L U E N O T E G R N R E D O R G B R N Y L W B L U C 1 G R N Y L W F A N S P E E D S W I T C H X 1 M 2 1 3 4 5 L N L N F 1 U G R N Y L W G R N Y L W M 1 Q 1 M 6 Connect the power supply and remote controller cables to the terminal 7 Attach ...

Page 23: ...rth wires have been connected properly and that the earth terminals are tightened Fuses circuit breakers or protection devices Check that the fuses circuit breakers or the locally installed protection devices are of the size and type specified in 4 4 Preparing electrical wiring 49 Be sure that neither a fuse nor a protection device has been bypassed Internal wiring Visually check the electrical co...

Page 24: ...1 Switch off the power supply 2 The air filter can be installed in 1 of 2 locations on this product side and bottom Remove the filter by sliding as shown below Horizontal installation Remove the filter by sliding min 200 mm Vertical installation Push the tabs at the filter and pull it back min 70 mm ...

Page 25: ...il units 3P443944 5P 2021 12 High floor standing Pull the filter and remove from the unit 3 Use a vacuum cleaner or wash air filter with water When the air filter is very dirty use a soft brush and neutral detergent 4 Set the air filter back to its original position ...

Page 26: ...instruction list Materials Item Electrical part fan motor capacitor 1 Aluminium fin copper tube galvanized steel plate brass 10 Plastic 2 18 8 22 27 Plastic metal 3 17 24 Plastic frame plastic net 4 Galvanized steel 5 9 13 14 16 20 23 25 26 Galvanized steel plastic foam 6 7 11 12 15 19 Plastic foam 21 9 Technical data A subset of the latest technical data is available on the regional Daikin websit...

Page 27: ... 505 56 42 A B C D mm Units mm A B C D FWE03 05D 719 757 799 909 FWE06D 919 957 999 1109 FWE07 11D 1119 1157 1199 1309 Vertical outlook High floor standing type 136 220 711 561 501 418 404 79 129 112 175 206a mm a In case of high floor standing kit ESFH03D5 usage Floor standing outlook ...

Page 28: ...747 909 FWE06 919 957 947 1109 FWE07 11D 1119 1157 1147 1309 Additional drain pan ESFD01D6 CAUTION Make sure to attach the drain socket rubber after installing the additional drain pan Otherwise condensation on the main unit or water pipes air filter dirt or drain blockage may cause dripping resulting in fouling or failure of the object concerned Horizontal installation b c a a Additional drain pa...

Page 29: ...9 Technical data Installation manual 29 FWE03 11D Fan coil units 3P443944 5P 2021 12 Vertical installation c b a a Additional drain pan b Drain socket rubber c Drain socket ...

Page 30: ... 9 3 Wiring diagram On terminal English Translation Connection X1M Main terminal Field supply Protective earth Earth Field wire Fan motor cable WHT White GRN Green RED Red ORG Orange BRN Brown YLW Yellow BLU Blue GRN YLW Green yellow C1 Capacitor F1U Fuse X1M Terminal strip M Fan motor ...

Page 31: ......

Page 32: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P443944 5P 2021 12 Copyright 2019 Daikin Verantwortung für Energie und Umwelt ...

Reviews: