48
Engineering & Physical Data
Engineering Data - Chilled Water Fan Coil Unit
MODEL
FWKE05E
FWKE08E
HIGH
MEDIUM
LOW
QUIET
HIGH
MEDIUM
LOW
QUIET
NOMINAL COOLING CAPACITY
Btu/h
20100
15900
11900
8200
30000
24700
19800
15200
W
5900
4650
3500
2400
8800
7250
5800
4550
NOMINAL SENSIBLE COOLING CAPACITY
Btu/h
15400
11700
8700
5800
21900
18500
14500
11000
W
4510
3440
2540
1710
6430
5410
4260
3220
NOMINAL HEATING CAPACITY
(ENTERING WATER TEMP. = 50°C)
Btu/h
24200
19800
15200
11300
38200
30400
23900
18400
W
7100
5800
4450
3300
11200
8900
7000
5400
NOMINAL TOTAL INPUT POWER
W
37
19
12
7
90
50
26
17
NOMINAL RUNNING CURRENT
A
0.26
0.19
0.13
0.11
0.74
0.43
0.28
0.19
POWER SOURCE
V/Ph/Hz
220-240 / 1 / 50
REFRIGERANT TYPE
N/A
INDOOR UNIT
CONTROL
AIR DISCHARGE
4 WAY AUTOMATIC LOUVER (UP & DOWN)
OPERATION
LCD WIRELESS MICRO-COMPUTER REMOTE CONTROL
AIR FLOW
CFM
620
470
350
220
890
720
560
420
NOMINAL WATER FLOW RATE
USGPM
4.52
3.56
2.68
1.84
6.74
5.55
4.44
3.41
litres/min
17.10
13.48
10.15
6.96
25.51
21.02
16.81
12.90
HEAD LOSS (COOLING)
kPa
24
15
10
5
20
14
9
7
HEAD LOSS (HEATING) : 50°C
kPa
21
13
8
4
18
12
8
5
MAX. WORKING PRESSURE
kPa
1608
SURFACE AIR VELOCITY
m/s
0.64
0.60
0.42
0.27
0.81
0.68
0.55
0.43
SOUND PRESSURE LEVEL (H/M/L)
dBA
37
31
23
16
47
42
37
31
UNIT DIMENSION - ( ) WITH
PANEL
H X W X D
mm
265 X 820 X 820 (340 X 990 X 990)
PACKING DIMENSION - ( ) PANEL
H X W X D
mm
341 X 916 X 916 (125 X 1020 X 1020)
UNIT WEIGHT (UNIT + PANEL)
kg
26 + 4
28 + 4
CONDENSATE DRAIN SIZE
mm
19.05
PIPE CONNECTION
mm
19.05
FAN
TYPE
TURBO FAN
DRIVE
DIRECT
FAN SPEED
RPM
450
360
280
200
660
550
440
350
FAN EFFICIENCY
%
50.3
51.3
37.4
22.0
51.9
52.6
49.6
40.5
FAN MOTOR
TYPE
BLDC
INDEX OF PROTECTION (IP)
IP20
INSULATION GRADE
E
RATED INPUT POWER
W
37
19
12
7
90
50
26
17
RATED RUNNING CURRENT
A
0.26
0.19
0.13
0.11
0.74
0.43
0.28
0.19
STARTING CURRENT
A
1.5
2.2
MOTOR OUTPUT
W
70
70
MOTOR EFFICIENCY
%
70.0
70.0
70.0
70.0
75.0
75.0
75.0
75.0
POLES
8
COIL
TUBE
MATERIAL
COPPER
DIAMETER
mm
7.00
FIN
MATERIAL
ALUMINIUM
FACE AREA
m
2
0.39
0.37
ROW
2
3
WATER VOLUME
litre
1.36
1.97
AIR
QUALITY
FILTER
TYPE
WASHABLE SARANET FILTER
QUANTITY
pc
1
CASING
COLOUR
LIGHT GREY
NOTE:
A) BASED ON EUROVENT CONDITIONS
B) ADDITIONAL 10W IS REQUIRED FOR CONDENSATE DRAIN PUMP
C) SOUND PRESSURE LEVEL IS TESTED AS PER JIS STANDARD AS BELOW:
FWKE05E MODEL - 1.4M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
FWKE08/11E MODEL - 1.5M BELOW THE FACE CENTER OF AIR RETURN OF THE UNIT
MODE
COOLING
HEATING
ENTERING AIR TEMPERATURE
27°C DB / 19°C WB
20°C DB
ENTERING WATER TEMPERATURE
7°C
50°C (2 Pipes System)
70°C (4 Pipes System)
LEAVING WATER TEMPERATURE
12°C
60°C (4 Pipes System)
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Summary of Contents for FWMT Series
Page 2: ......
Page 57: ...Outlines Dimensions 54 Model FWMT05 06C Note Dimension in mm...
Page 72: ...69 Wiring Diagrams Wiring Diagrams Model FWMT02 03 04 05 06C...
Page 73: ...70 Wiring Diagrams Model FWJC6 8 9 11 13B...
Page 74: ...71 Wiring Diagrams Model FWJCC2 4 5B...
Page 75: ...72 Wiring Diagrams Model FWKE05 08E...
Page 76: ...73 Wiring Diagrams Model FWKE11E...
Page 77: ...74 Wiring Diagrams Model FWPMM3 4 6 7A With Controller...
Page 78: ...75 Wiring Diagrams Model FWPMM9 11 12 14 16A With Controller...
Page 79: ...76 Wiring Diagrams Model FWPMM3 4 6 7A Without Controller...
Page 80: ...77 Wiring Diagrams Model FWPMM9 11 12 14 16A Without Controller...
Page 81: ...78 Wiring Diagrams Model UAHMM20A...
Page 82: ...79 Wiring Diagrams Model UAHMM25A...