FWV-L-M
54
9
RATED TECHNICAL DATA
» Rated technical data - 2 pipes
FWV-FWL-FWM
01
15
02
Speed
min
med
max
min
med
max
min
med
max
Total cooling capacity
(1)(E)
kW
1,02
1,21
1,50
1,24
1,48
1,69
1,34
1,66
1,91
Sensible cooling capacity
(1)(E)
kW
0,77
0,94
1,16
0,93
1,10
1,25
0,98
1,20
1,37
FCEER class
(E)
E
Water flow
(2)
l/h
176
208
258
214
255
291
231
286
329
Water pressure drop
(2)(E)
kPa
7
9
13
8
11
14
7
10
13
Heating capacity
(3)(E)
kW
1,21
1,48
1,82
1,45
1,72
1,84
1,50
1,81
2,15
FCCOP class
(E)
E
Water flow
(3)
l/h
208
255
313
250
296
317
258
312
370
Water pressure drop
(3)(E)
kPa
8
11
15
9
12
14
6
9
12
Rated air flow
m³/h
167
233
319
210
271
344
214
271
344
Power input
(E)
W
21
28
37
25
36
53
24
36
53
Total sound power level
(4)(E)
dB(A)
37
42
47
38
44
49
40
44
50
Sound pressure level
(5)(E)
dB(A)
32
37
42
33
39
44
35
39
45
n° of fans
1
1
1
Water connections - standard coil
“
1/2
Water content - standard coil
dm³
0,46
0,46
0,70
FWV-FWL-FWM
25
03
35
Speed
min
med
max
min
med
max
min
med
max
Total cooling capacity
(1)(E)
kW
1,57
1,99
2,36
1,73
2,34
2,87
1,94
2,58
3,45
Sensible cooling capacity
(1)(E)
kW
1,15
1,53
1,82
1,23
1,66
2,05
1,41
1,99
2,69
FCEER class
(E)
E
D
E
Water flow
(2)
l/h
270
343
406
298
403
494
334
444
594
Water pressure drop
(2)(E)
kPa
8
12
16
6
9
13
4
7
12
Heating capacity
(3)(E)
kW
1,74
2,26
2,70
1,76
2,37
2,94
2,39
3,13
4,05
FCCOP class
(E)
E
Water flow
(3)
l/h
300
389
465
303
408
506
412
539
697
Water pressure drop
(3)(E)
kPa
8
12
17
5
8
11
5
8
13
Rated air flow
m³/h
267
341
442
293
341
442
331
450
640
Power input
(E)
W
29
44
57
29
43
56
40
50
65
Total sound power level
(4)(E)
dB(A)
35
43
48
36
42
48
35
43
52
Sound pressure level
(5)(E)
dB(A)
30
38
43
31
37
43
30
38
47
n° of fans
2
2
2
Water connections - standard coil
“
1/2
Water content - standard coil
dm³
0,71
1,06
0,95
FWV-FWL-FWM
04
06
08
10
Speed
min
med
max
min
med
max
min
med
max
min
med
max
Total cooling capacity
(1)(E)
kW
2,47
3,21
4,23
2,95
3,59
4,41
3,88
5,14
6,53
4,00
6,07
7,78
Sensible cooling capacity
(1)(E)
kW
1,76
2,39
3,05
2,27
2,85
3,55
2,75
3,70
4,73
2,94
4,46
5,72
FCEER class
(E)
D
D
E
E
Water flow
(2)
l/h
425
553
728
508
618
759
668
885
1124
689
1045
1340
Water pressure drop
(2)(E)
kPa
5
8
12
7
10
14
5
9
12
6
13
20
Heating capacity
(3)(E)
kW
2,47
3,24
4,24
3,31
4,08
4,98
3,97
5,17
6,49
4,39
6,53
8,37
FCCOP class
(E)
E
E
E
Water flow
(3)
l/h
425
558
730
570
703
858
684
890
1118
756
1124
1441
Water pressure drop
(3)(E)
kPa
4
6
10
7
10
14
4
7
10
6
12
18
Rated air flow
m³/h
420
497
706
527
605
785
661
771
1011
682
1022
1393
Power input
(E)
W
38
61
98
47
68
98
86
127
182
109
169
244
Total sound power level
(4)(E)
dB(A)
35
43
53
43
49
56
47
54
61
49
60
67
Sound pressure level
(5)(E)
dB(A)
30
38
48
38
44
51
42
49
56
44
55
62
n° of fans
2
2
2
2
Water connections - standard coil
“
1/2
1/2
3/4
3/4
Water content - standard coil
dm³
1,42
1,43
2,15
2,15
(1) Water temperature 7°C/12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity) according to EN1397:2021
(2) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity)
(3) Water temperature 45°C / 40°C, air temperature 20°C
(4) Sound power measured according to standards ISO 3741 and ISO 3742
(5) Sound pressure measured at a distance of 4 m in a free field with a directivity factor of 1
(E) EUROVENT certified data
Power supply 230-1-50 (V-ph-Hz)