Control Devices
EDUS391000-C
18
Controls
System Configuration (Group / Zone Control)
Group control
The group means the indoor units connected by the same control wiring for remote controller (connected to terminal
P1 and P2) and all the unit in group have “the same setting” and “the same operation”.
The indoor units in the group are controlled by the remote controller for indoor unit.
The number of indoor units in one group is up to 16 units.
Zone control
The zone means the indoor units connected by the same control wiring for central remote controller (connected to
terminal F1 and F2) and all the unit in zone have “the same setting”.
The zone control of the indoor unit is operated by the central remote controller.
From 1 up to 64 zones can be controlled by the central remote controller.
The number of groups you can set in one zone is from 1 up to 64 groups.
Up to 16 units can be set in one group, and up to 64 groups (up to 128 units) can be connected.
Summary of Contents for FXAQ-MVJU
Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls ...
Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features ...
Page 64: ...EDUS391000 C Control Devices Controls 63 ...
Page 65: ...Control Devices EDUS391000 C 64 Controls ...
Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A ...
Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B ...
Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360 ...
Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360 ...
Page 76: ...EDUS391000 C Adapter Controls 75 1P013360 ...
Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A ...
Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A ...
Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow ...
Page 82: ...EDUS391000 C Adapter Controls 81 ...
Page 83: ...Adapter EDUS391000 C 82 Controls ...
Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221 ...