EDUS391000-C
Control Devices
Controls
29
2.4.5
Wiring Instructions
Wiring instructions
For control wiring of DIII-NET, you can select from the following 3 types of wiring methods.
1. Series method :
Wiring is connected by a single line from the central controller.
2. Bus method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
3. Star method :
Up to 16 branches is possible. Never diverge the sub-branches from the branch line.
Specifications of Transmission Wiring
Be sure to use either 2-core sheathed vinyl cord or cable as mentioned below. The size of wire should be selected in the
range of AWG 18 or AWG 16.
<Length of control wiring>
Between central remote controller and air-conditioner
Maximum extension : 3280 ft, Total length : 6560 ft (
)
When you have branches, be sure the total length includes all the branches.
Summary of Contents for FXAQ-MVJU
Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls ...
Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features ...
Page 64: ...EDUS391000 C Control Devices Controls 63 ...
Page 65: ...Control Devices EDUS391000 C 64 Controls ...
Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A ...
Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B ...
Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360 ...
Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360 ...
Page 76: ...EDUS391000 C Adapter Controls 75 1P013360 ...
Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A ...
Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A ...
Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow ...
Page 82: ...EDUS391000 C Adapter Controls 81 ...
Page 83: ...Adapter EDUS391000 C 82 Controls ...
Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221 ...