EDUS391000-C
Control Devices
Controls
31
<Cautions>
Even in the system without remote control, connect the remote controller once to set group No. for central control
equipment and remove the remote controller after setting.
When you set the group No., be sure to supply the power to the central remote controller, the unified ON/OFF
controller and the indoor unit.
<Example of group setting>
Cautions
When the power is supplied, all the display appears once on the remote controller and then the display changes to [88]
for about one minute and during that time the remote controller does not function. However, this is not a malfunction of
remote controller.
Control Mode Setting by Remote Controller (Field Setting)
The control mode defines the function of local remote controllers to handle various types of control and applications.
Function can be defined by conditions and combinations of local remote control operations such as ON/OFF etc. (See
table below.)
Operation can always carried out from the central remote controller. (Except when connected to the central monitoring
panel.)
Description of Control Mode
The following 5 operation control modes and 20 modes combined with temperature and operation mode setting by the
remote controller are set and display by the control mode of 0 through 19.
Remote Control Rejection
For when you want to turn on/off using central remote controller only.
(On/off cannot be carried out by remote controller.)
Remote Controller Off Only Accepted
For when you want to turn on only by the central remote controller, and turn off only by local remote controller.
Central Priority
For when you want to turn on only by the central remote controller, and during the set time, turn on/off freely by local
remote controller.
Individual Priority (Last Command Priority)
For when you want to turn on/off by both central remote controller and local remote controller.
Remote Controller Permission Timer
For when you want to turn on/off by local remote controller during set time, but you do not want to start operation from
the central remote controller at the programmed time of system start.
Note:
The control mode consists of numbers 0 through 19, but only 0 through 9 are usually set.
Summary of Contents for FXAQ-MVJU
Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls ...
Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features ...
Page 64: ...EDUS391000 C Control Devices Controls 63 ...
Page 65: ...Control Devices EDUS391000 C 64 Controls ...
Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A ...
Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B ...
Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360 ...
Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360 ...
Page 76: ...EDUS391000 C Adapter Controls 75 1P013360 ...
Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A ...
Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A ...
Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow ...
Page 82: ...EDUS391000 C Adapter Controls 81 ...
Page 83: ...Adapter EDUS391000 C 82 Controls ...
Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221 ...