background image

8 Troubleshooting

Installation and operation manual

11

FXDA10~63A2VEB
VRV system air conditioner
3P599562-1 – 2020.05

NOTICE

The  R32  refrigerant  leakage  sensor  is  a  semiconductor
detector  which  may  incorrectly  detect  substances  other
than  R32  refrigerant.  Avoid  using  chemical  substances
(e.g.  organic  solvents,  hair  spray,  paint)  in  high
concentrations,  in  the  close  proximity  of  the  indoor  unit
because  this  may  cause  misdetection  of  the  R32
refrigerant leakage sensor.

INFORMATION

Lifetime  of  the  sensor  is  10  years.  The  user  interface
displays  error  "

CH-05

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-02

"  after  the  end  of  the

sensor lifetime. For more information refer to the reference
guide of the user interface and contact you dealer.

In case of detection when the unit is standby

When the detection occurs when the unit is standby, "false detection
check" will occur.

False detection check

1

Unit starts fan operation on the lowest setting.

2

User  interface  displays  error  code  "

A0-13

",  emits  alarm  sound

and status indicator is blinking.

3

Sensor checks if refrigerant leakage or misdetection occurred.

▪ If refrigerant leakage is NOT detected, 

Result: 

 system returns to

normal operation after approximately 2 minutes.

▪ If refrigerant leakage is detected, 

Result:

1

User  interface  displays  error  "

A0-11

",  emits  alarm  sound  and

status indicator is blinking.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

In case of detection when the unit is turned on

1

User  interface  displays  error  "

A0-11

",  emits  alarm  sound  and

status indicator is blinking.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

INFORMATION

To stop alarm of the user interface see the reference guide
of the user interface.

INFORMATION

The minimum airflow during normal operation or during the
refrigerant leakage detection is always >240 m

3

/h.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
circuit breaker or a residual current
device frequently actuates or the ON/
OFF switch does NOT function properly.

Turn OFF all main power
supply switches to the
unit.

If water leaks from the unit.

Stop operation.

The operation switch does NOT function
properly.

Turn OFF the power
supply.

If the user interface displays 

.

Notify your installer and
report the error code. To
display an error code see
the reference guide of the
user interface.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

INFORMATION

Refer  to  the  reference  guide  located  on 

http://

www.daikineurope.com/support-and-manuals/product-
information/

 for more troubleshooting tips.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Summary of Contents for FXDA10A2VEB

Page 1: ...and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXDA10A2VEB FXDA15A2VEB FXDA20A2VEB FXDA25A2VEB FXDA32A2VEB FXDA40A2VEB FXDA50A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...ndoor unit 17 15 Commissioning 18 15 1 Checklist before commissioning 18 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unif...

Page 4: ...ill not come into direct contact with people Do NOT use booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 419 Refrigerant piping installatio...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...or your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the un...

Page 8: ...discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press...

Page 9: ...ver replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check...

Page 10: ...r to ensure smoother operation As soon as the power is turned on the user interface display appears Insert batteries in the user interface if applicable 7 5 About the refrigerant This product contains...

Page 11: ...INFORMATION The minimum airflow during normal operation or during the refrigerant leakage detection is always 240 m3 h 8 Troubleshooting If one of the following malfunctions occur take the measures sh...

Page 12: ...tion in an environment with a lot of organic solvents such as ink and siloxane WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an op...

Page 13: ...door unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the opt...

Page 14: ...wooden structure separate the duct and wall electrically Install the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Use...

Page 15: ...and T joints with the correct gauge for the operating capacity of the units 100 600 mm a a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might ca...

Page 16: ...of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet completed 416 13 Piping installation 13 1 P...

Page 17: ...rom the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 14 Electrical installation DANGER RISK OF ELECTROCU...

Page 18: ...1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 N L a d c b L N N L N L N L a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NO...

Page 19: ...x 3 0 02 3 0 x 3 5 03 Setting Static pressure Change the value number in accordance with the external static pressure of the duct to be connected as in the table below See technical documentation for...

Page 20: ...subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication req...

Page 21: ...ker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant le...

Page 22: ......

Page 23: ......

Page 24: ...3P599562 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: