11 About the box
Installation and operation manual
12
FXDA10~63A2VEB
VRV system air conditioner
3P599562-1 – 2020.05
For the installer
11
About the box
11.1
Indoor unit
11.1.1
To remove the accessories from the
indoor unit
C
A
B
1×
a
1×
b
c
1×
C
A
B
1×
1×
26×
8×
1×
1×
2×
C
e
d
f
g
h
i
1×
1×
4×
8×
4×
j
k
l
m
A
On the unit
a
Installation and operation manual
b
General safety precautions
B
On the bottom of the packing box
c
Air filter
C
In the fan motor space
d
Washers for hanger bracket
e
Screws for duct flanges
f
Metal clamp
g
Sealing pads: middle and large
h
Drain hose
i
Sealing material
j
Insulation piece: Small (liquid pipe)
k
Insulation piece: Large (gas pipe)
l
Tie wraps: small and large
m
Washer fixing plate
12
Unit installation
12.1
Preparing the installation site
Avoid installation in an environment with a lot of organic solvents
such as ink and siloxane.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
12.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
▪
Spacing
. Mind the following requirements:
c
c
d
≥620
200
e
≥240
A
≥20
≥300
b
≥300
b
f
a
(mm)
≥400
A
Minimum distance to the floor:
2.7 m
to avoid accidental touching.
2.5 m
in case the fan is covered (e.g. false ceiling, grille,
…)
a
Control box
b
Maintenance space
c
Ceiling
d
Ceiling opening
e
Select the dimension to ensure downward slope of at
least 1/100
f
Floor surface
▪
Discharge grille.
Minimum requirement installation height of
discharge grille ≥1.8 m.
▪
Ceiling opening size.
Make sure the ceiling opening is within the
following limits:
A
620
(mm)
12‒1 Ceiling opening dimension (A)
Class
A (mm)
10~32
790
40~50
990
63
1190