16 Configuration
Installation and operation manual
19
FXDA10~63A2VEB
VRV system air conditioner
3P599562-1 – 2020.05
The
fuses
or locally installed protection devices are
installed according to this document, and have NOT been
bypassed.
The
power supply voltage
matches the voltage on the
identification label of the unit.
There are NO
loose connections
or damaged electrical
components in the switch box.
There are NO
damaged components
or
squeezed
pipes
on the inside of the indoor and outdoor units.
The
stop valves
(gas and liquid) on the outdoor unit are
fully open.
15.2
To perform a test run
INFORMATION
▪ Perform the test run according to the instructions in the
outdoor unit manual.
▪ The test run is only completed if there is no malfunction
code displayed on the user interface or the outdoor unit
7‑segment display.
▪ See the service manual for the complete list of error
codes and a detailed troubleshooting guideline for each
error.
NOTICE
Do NOT interrupt the test run.
16
Configuration
16.1
Field setting
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
▪ Ceiling height
▪ Static pressure
▪ Air volume when thermostat control is OFF
▪ Time to clean air filter
▪ Thermostat sensor selection
▪ Differential for automatic changeover
▪ Auto-restart after power failure
INFORMATION
▪ The fan speed of the indoor unit is preset to ensure the
standard external static pressure.
▪ To set a higher or lower external static pressure, reset
the initial setting with the user interface.
Setting: Ceiling height
This setting must correspond with the actual distance to the floor,
capacity class and air flow directions.
If the distance to the floor is (m)
Then
(1)
M
SW
—
≤2.7
13 (23)
0
01
2.7<x≤3.0
02
3.0<x≤3.5
03
Setting: Static pressure
Change the value number (—) in accordance with the external static
pressure of the duct to be connected as in the table below. See
technical documentation for details.
Setting
(1)
External static pressure
M
SW
—
13(23)
5
01
Standard
02
High static pressure setting
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1
If you have set the fan to operate, set the air volume speed:
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
(a)
Only use in combination with optional remote sensor or when
setting
M
10 (20),
SW
2, —
3 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which
"Time to clean filter"
notification
is displayed on the user interface.
If you want an interval of…
(air contamination)
Then
(1)
M
SW
—
±2500 h (light)
10 (20)
0
01
±1250 h (heavy)
02
Notification ON
3
01
Notification OFF
02
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
thermostat sensor is used.
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
• —: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
Setup volume
: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
•
Monitoring 1, 2
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1) or by
L
(Monitoring 2).