FXDQ-SPV1 EDTFVN391825
13
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Model
Capacity
indication
Indoor air temp.
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
FXDQ20SPV1
20
1.9
1.8
2.1
1.8
2.2
1.7
2.2
1.6
2.2
1.6
2.3
1.4
2.3
1.3
FXDQ25SPV1
25
2.5
2.2
2.6
2.2
2.8
2.2
2.8
2.0
2.8
1.9
2.9
1.8
3.0
1.7
FXDQ32SPV1
32
3.2
2.6
3.4
2.8
3.5
2.9
3.6
2.6
3.6
2.6
3.7
2.3
3.8
2.2
FXDQ40SPV1
40
4.0
3.5
4.2
3.7
4.4
3.7
4.5
3.4
4.6
3.2
4.7
3.0
4.8
2.8
FXDQ50SPV1
50
4.9
4.0
5.3
4.3
5.5
4.5
5.6
4.1
5.7
4.0
5.8
3.6
5.9
3.4
FXDQ63SPV1
63
6.3
5.2
6.7
5.6
7.0
5.5
7.1
5.1
7.2
4.9
7.3
4.5
7.5
4.2
TC: Total capacity: kW
SHC: Sensible heat capacity: kW
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
8.2 Cooling Capacity for Te: 6°C
Model
Capacity
indication
Indoor air temp.
14°CWB
16°CWB
18°CWB
19°CWB
20°CWB
22°CWB
24°CWB
20°CDB
23°CDB
26°CDB
27°CDB
28°CDB
30°CDB
32°CDB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
FXDQ20SPV1
20
1.1
1.0
1.5
1.3
2.0
1.5
2.2
1.6
2.4
1.7
2.9
1.8
3.4
1.9
FXDQ25SPV1
25
1.5
1.3
2.0
1.6
2.5
1.9
2.8
2.0
3.1
2.1
3.7
2.3
4.4
2.5
FXDQ32SPV1
32
1.9
1.7
2.5
2.1
3.2
2.5
3.6
2.6
4.0
2.8
4.8
3.0
5.6
3.2
FXDQ40SPV1
40
2.3
2.2
3.2
2.7
4.0
3.2
4.5
3.4
5.0
3.5
5.9
3.8
6.9
4.0
FXDQ50SPV1
50
3.0
2.7
4.0
3.3
5.0
3.9
5.6
4.1
6.1
4.3
7.3
4.6
8.5
4.9
FXDQ63SPV1
63
3.8
3.3
5.0
4.1
6.4
4.8
7.1
5.1
7.8
5.3
9.3
5.7
10.9
6.1
TC: Total capacity: kW
SHC: Sensible heat capacity: kW
Notes:
1. These capacity tables are for use when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system
satisfies the required heat load.
2.
shows rated condition.
Summary of Contents for FXDQ-SPV1
Page 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...
Page 2: ......
Page 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...
Page 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...
Page 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...
Page 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...
Page 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...
Page 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...
Page 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...
Page 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...
Page 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...
Page 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...
Page 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...
Page 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...
Page 41: ......
Page 42: ......
Page 43: ......