background image

FXDQ-SPV1 EDTFVN391825

31

3P347455-11H

6

(2) When the pipe work is completed, please confirm 

     whether any air is leaked out.

Heat insulation of the pipe on the liquid side

Heat insulation piece for 

the pipe (Main unit side)

Heat insulation piece (3) for the 

connector (Accessory)

Flare nut connection section

Close firmly to the unit body

The connecting seam 

facing upward

Main unit

Banding tie (9) 

(Accessory)

Heat insulation piece for 

the pipe (supplied on site)

Pipe on the liquid side

Pipe on the air supply side

Heat insulation of the pipe on the air supply side

Heat insulation 

piece for the pipe 

(main unit side)

Heat insulation piece (4) for the connector

(Accessory)

Flare nut 

connection section

The connecting 

seam facing upward

Middle seal (6)

(Accessory)

Close firmly to 

the unit body

Main unit

Banding tie (9)

(Accessory)

Heat insulation piece for 

the pipe (supplied on site)

Wrap on the 

flare nut connector.

Fig. 8

Table 2

Pipe dimension

Angle to be further tightened

Recommended length 

of the tool arm

60 to 90 degrees
60 to 90 degrees
30 to 60 degrees
30 to 60 degrees

About 150 mm
About 200 mm
About 250 mm
About 300 mm

Ø 6.4 (1/4”)
Ø 9.5 (3/8”)

Ø 12.7 (1/2”)
Ø 15.9 (5/8”)

(3) When it is checked that no air is leaked out, please 

     refer to Fig. 8 to properly insulate the pipe 

     connections with heat insulation material.

· 

When carrying out heat insulation work, please use 

   the supplied heat insulation piece (3) (4) for the pipe 

   of the liquid side and the air supply side. In addition, 

   the connecting seams of the heat insulation piece (3) 

   and (4) for the connector shall face upward. (Please 

   use banding tie (9) to clamp both ends.)

· 

Please use the middle seal (6) to wrap the surface of 

   the heat insulation piece (4) for the connector on the 

   pipe of the air supply side. (The flare nut section)

The pipe supplied on site must be heat insulated to the 

connecting section of the pipe. In case that the pipe is 

exposed, condensate can occur, and injury from burning 

can also happen if touched.

CAUTION

· 

Before welding the refrigerant pipe, please firstly carry 

   out nitrogen exchange, or when welding (Caution 2), 

   fill in nitrogen (Caution 1) in the refrigerant pipe, and 

   finally use the flare to connect to the indoor unit.

   

(Refer to Fig. 9)

CAUTION

1. In case that nitrogen is filled into the pipe when welding, 

    a relief valve shall be used to control the pressure to 

    0.02 MPa (0.2 kgf/cm

2

) (as if breeze flows along your 

    cheek).

2. When welding the connection section of the refrigerant 

    pipe, never use any welding flux. Please use phosphorus 

    and bronze brazing material (BCuP-2: JIS Z 3264/

    BCu93P-710/795: ISO 3677) which does not need 

    welding flux. (In case that any welding flux containing 

    chlorine is used, the pipe can be corroded; and in case 

    that any welding flux containing fluorin is used, the ester 

    oil or ether oil can be deteriorated, and the refrigerant pipe 

    system can be further influenced.)

Welding position

Relief valve

Wrapping

Nitrogen

Nitrogen

Refrigerant pipe

Manual

valve

Fig. 9

7. DRAIN PIPING WORK

CAUTION

· 

The connecting interface of the water drainage pipe 

   varies depending on different types, so please confirm 

   the name of the type, and use the installation method 

   suitable for the type.

(1) Install the water drainage pipe.

Case for Model FXDQ ~ SPV1

Connecting interface of 

the water drainage pipe

Refrigerant pipe

Water drainage port for maintenance

(With a rubber plug)

· 

When installing the water drainage pipe, ensure that 

   the water drainage is smooth.

· 

The diameter of the water drainage pipe shall be larger 

   than or equal to that of the connection pipe (polyethylene 

   pipe; pipe dimensions: 20 mm; outer diameter: 26 mm).

   (Not including the riser pipe)

Summary of Contents for FXDQ-SPV1

Page 1: ...FXDQ SPV1 EDTFVN391825 201803 Engineering Data 50 Hz...

Page 2: ......

Page 3: ...ams 10 6 Electric Characteristics 11 7 Safety Devices Setting 12 8 Capacity Tables 13 8 1 Cooling Capacity for Te Auto 13 8 2 Cooling Capacity for Te 6 C 13 8 3 Cooling Capacity for Te 9 C 14 8 4 Heat...

Page 4: ...5 2 1 Lineup Capacity range 2 2 kW 2 8 kW 3 6 kW 4 5 kW 5 6 kW 7 1 kW 0 8 HP 1 HP 1 25 HP 1 6 HP 2 HP 2 5 HP Capacity index 20 25 31 25 40 50 62 5 FXDQ 20SPV1 25SPV1 32SPV1 40SPV1 50SPV1 63SPV1 V1 1 p...

Page 5: ...tion manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wa...

Page 6: ...manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Washers...

Page 7: ...on manual Drain hose Sealing pads Clamps Washers Insulation for fitting Metal clamp Washer fixing plate Screws for duct flanges Operation manual Installation manual Drain hose Sealing pads Clamps Wash...

Page 8: ...FXDQ SPV1 EDTFVN391825 6 3 Dimensions FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 3D071829D Unit mm...

Page 9: ...FXDQ SPV1 EDTFVN391825 7 FXDQ40SPV1 FXDQ50SPV1 3D071831D Unit mm...

Page 10: ...FXDQ SPV1 EDTFVN391825 8 FXDQ63SPV1 3D071830D Unit mm...

Page 11: ...iagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 12...

Page 12: ...FXDQ SPV1 EDTFVN391825 10 5 Wiring Diagrams FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 3D099151...

Page 13: ...FXDQ SPV1 EDTFVN391825 11 6 Electric Characteristics FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 4D090515...

Page 14: ...50 V 5 A Fan motor thermal fuse C Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Model FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Printed circuit board fuse A1P 250 V 5 A...

Page 15: ...gth Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 C...

Page 16: ...These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and pip...

Page 17: ...FXDQ SPV1 EDTFVN391825 15 9 Fan Performances FXDQ20SPV1 3D072697C...

Page 18: ...FXDQ SPV1 EDTFVN391825 16 FXDQ25SPV1 3D072698C...

Page 19: ...FXDQ SPV1 EDTFVN391825 17 FXDQ32SPV1 3D090527...

Page 20: ...FXDQ SPV1 EDTFVN391825 18 FXDQ40SPV1 FXDQ50SPV1 3D072702C...

Page 21: ...FXDQ SPV1 EDTFVN391825 19 FXDQ63SPV1 3D090542...

Page 22: ...FXDQ SPV1 EDTFVN391825 20 10 Sound Levels FXDQ20SPV1 FXDQ25SPV1 4D090507A 4D090508A...

Page 23: ...FXDQ SPV1 EDTFVN391825 21 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D090509A 4D090510A...

Page 24: ...FXDQ SPV1 EDTFVN391825 22 FXDQ63SPV1 4D090511A...

Page 25: ...FXDQ SPV1 EDTFVN391825 23 11 Centre of Gravity FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 4D072718G Unit mm 4D072719G Unit mm...

Page 26: ...FXDQ SPV1 EDTFVN391825 24 FXDQ63SPV1 4D072720H Unit mm...

Page 27: ...s Item Model FXDQ20SPV1 FXDQ25SPV1 FXDQ32SPV1 FXDQ40SPV1 FXDQ50SPV1 FXDQ63SPV1 Remote controller Wireless Cooling Only BRC4C66 Heat Pump BRC4C65 Wired BRC1C62 Navigation remote controller Wired remote...

Page 28: ...ctrical shock or fire Use cables with the specified specifications and all the cables shall be reliably connected and the wiring terminals and the cables are not tensioned by any external force Poor w...

Page 29: ...ting methods of the various functions as well as the temperature adjustment methods of the air conditioner to the user and ask the user to read the operation manual and carry out operations at the sam...

Page 30: ...y drained off The strength of the ceiling can withstand the weight of the indoor unit The ceiling is not obviously tilted There is no hazard of possible leakage of combustible gas There is enough spac...

Page 31: ...an be built in the new ceiling and other items purchased in the market can be used Please refer to Fig 3 Fig 3 Top ceiling Pile anchor screw Long nut or screw thread device Hoisting bolt Note The leng...

Page 32: ...r air exchange 1 Connect the pipe Refrigerant has been filled in the outdoor unit Align the connecting section of the refrigerant pipe to the center of the flare section and firstly turn 3 4 operation...

Page 33: ...pipe of the air supply side The flare nut section The pipe supplied on site must be heat insulated to the connecting section of the pipe In case that the pipe is exposed condensate can occur and inju...

Page 34: ...ng band Water drainage hose 2 Large seal 5 Accessory Metal clip 1 Accessory 4mm Precautions on installing the water drainage riser pipe Case for Model FXDQ SPV1 Please confirm that the height of the w...

Page 35: ...e air conditioner Point 12 14 or 16 Use sealing materials such as aluminum adhesive tape to seal the connection section between the flange and the air pipe on the air inlet side so as to prevent air l...

Page 36: ...is within a place easily in contact with people please install an electricity leakage circuit breaker to prevent electrical shock 4 When an electricity leakage circuit breaker is used please use a dev...

Page 37: ...ng cable to the electrical box When connecting the cables the cables shall be routed orderly and placed even and the electrical box cover shall not be supported up and the electrical box cover shall b...

Page 38: ...auses as loosened cables When connected to the terminal board please use round wiring terminal with insulated sleeve In case that round wiring terminal with insulated sleeve cannot be used connect the...

Page 39: ...Electrical Wiring Work 3 Remove the electrical box cover 4 Connect remote control 2 Slave to the terminal board of the remote control cable in the electrical box P1 and P2 No polarity 1 P 2 P 1 F 2 F...

Page 40: ...Setting the time to display the clean air filter element signal To change the Setting for contamination level of the air filter element tell the following contents to the user The factory setting to d...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...rts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of...

Reviews: