background image

English

13

11. FIELD SETTING AND TEST RUN

Field settings may have to be performed using the

remote controller, depending on the type of installation.

(1) Make sure the control box lids are closed on the indoor 

and outdoor units.

(2) Depending on the type of installation, make the field

settings from the remote controller after the power is
turned on, following the “Field Settings” manual which 
came with the remote controller.

The settings can select “Mode No.”, “FIRST CODE NO.”
and “SECOND CODE NO.”.

The “Field Settings” included with the remote controller
lists the order of the settings and method of operation.

Lastly, make sure the customer keeps the “Field Settings”
manual, along with the operating manual, in a safe place.

11-1 SETTING THE STATIC PRESSURE SELECTION

Select the SECOND CODE NO. for the resistance of the con-
nected duct.
(The SECOND CODE NO. is set to “01” when shipped.)

See the technical documentation for details.

11-2 REMOTE CONTROL SETTING

Forced off and ON/OFF operation should be selected by
selecting the SECOND CODE  NO. as shown in the table
below.
(The SECOND CODE NO. is set to “01” when shipped.)

Input A of forced off and ON/OFF operation work as shown in
the table below.

11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL

Explain the following to the customer if the filter dirt settings
have been changed.

The filter sign display time is set to 2500 hours
(equivalent to 1 year’s use) when shipped.

The settings can be changed to not display.

When installing the unit in a place with much dusts, set the fil-
ter sign display time to shorter intervals (1,250 hours).

Explain it to the customer that the filter needs to be cleaned
regularly to prevent clogging and also the time that is set.

11-4 SETTINGS FOR SEPARATELY SOLD

ACCESSORIES

See the instruction manuals included with separately sold
accessories for the necessary settings.

When using a wireless remote controller 

A wireless remote controller address needs to be set when
using a wireless remote controller. See the installation man-
ual included with the wireless remote controller for details on
how to make the settings.

(3) Perform a test run according to the outdoor unit’s

installation manual.

The operation lamp of the remote controller will flash
when a malfunction occurs. Check the malfunction code
on the liquid crystal display to identify the point of trouble. 
An explanation of malfunction codes and the correspond-
ing trouble is provided in “CAUTION FOR SERVICING”
of the outdoor unit.
If the display shows any of the following, there is a possi-
bility that the wiring was done incorrectly or that the
power is not on, so check again.

CAUTION

Always stop the test run using the remote controller to stop
operation.

(4) After finishing the test run, make sure to check drain-

age in the drain pump according to “7. DRAIN PIPING
WORK”.

External static 

pressure

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Standard 

(10Pa)

13(23)

5

01

High static pres-

sure setting 

(30Pa)

02

External ON/OFF input

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Forced off

12(22)

1

01

ON/OFF operation

02

Forced off

ON/OFF operation

Input A “on” to force a stop 
(remote controller reception prohibited)

Unit operated by changing input A from 
“off” to “on”

Input A “off” to allow remote controller

Unit stopped by changing input A from “on” 
to “off”

SETTING

Mode No.

SECOND 
CODE NO.

FIELD SET 
MODE

FIRST 
CODE NO.

Mode No.

FIRST CODE NO.

SECOND 
CODE NO.

01

02

10 (20)

0

Filter dirt

low

high

1 (low/high)

Displayed time

(units: hours)

2500/

1250

10000/

5000

3

Filter sign 

display

ON

OFF

Remote control display

Content

”  display

• There is a short circuit at the FORCED

OFF terminals (T

1

, T

2

).

”  display

• The test-run has not been performed.

”  display

”  display

• The power on the outdoor unit is off.
• The outdoor unit has not been wired for 

power supply.

• Wiring is incorrect for the transmission

wiring and / or FORCED OFF wiring.

• The transmission wiring is cut.

”  display

• Reversed transmission wiring

No display

• The power on the indoor unit is off.
• The indoor unit has not been wired for

power supply.

• Wiring is incorrect for the remote con-

troller wiring, the transmission wiring
and / or the FORCED OFF wiring.

• The remote controller wiring is cut.

4PEN325876-1F.book  Page 13  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ20A2VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A2VEB FXDQ20A2VEB FXDQ25A2VEB FXDQ32A2VEB FXDQ40A2VEB FXDQ50A2VEB FXDQ63A2VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM...

Page 2: ...por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acord...

Page 3: ...lation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified pers...

Page 4: ...the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an...

Page 5: ...ould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If ther...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anch...

Page 7: ...a ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the t...

Page 8: ...Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluo...

Page 9: ...Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipi...

Page 10: ...on area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use a...

Page 11: ...o not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of p...

Page 12: ...ower sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...stem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 1...

Page 14: ...achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to th...

Page 15: ...n man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM...

Page 18: ...4P489744 1 2017 04 Copyright 2012 Daikin 4P489744 1 book Page 1 Thursday April 27 2017 4 42 PM...

Reviews: