English
13
11. FIELD SETTING AND TEST RUN
Field settings may have to be performed using the
remote controller, depending on the type of installation.
(1) Make sure the control box lids are closed on the indoor
and outdoor units.
(2) Depending on the type of installation, make the field
settings from the remote controller after the power is
turned on, following the “Field Settings” manual which
came with the remote controller.
•
The settings can select “Mode No.”, “FIRST CODE NO.”
and “SECOND CODE NO.”.
•
The “Field Settings” included with the remote controller
lists the order of the settings and method of operation.
•
Lastly, make sure the customer keeps the “Field Settings”
manual, along with the operating manual, in a safe place.
11-1 SETTING THE STATIC PRESSURE SELECTION
•
Select the SECOND CODE NO. for the resistance of the con-
nected duct.
(The SECOND CODE NO. is set to “01” when shipped.)
•
See the technical documentation for details.
11-2 REMOTE CONTROL SETTING
•
Forced off and ON/OFF operation should be selected by
selecting the SECOND CODE NO. as shown in the table
below.
(The SECOND CODE NO. is set to “01” when shipped.)
•
Input A of forced off and ON/OFF operation work as shown in
the table below.
11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL
•
Explain the following to the customer if the filter dirt settings
have been changed.
•
The filter sign display time is set to 2500 hours
(equivalent to 1 year’s use) when shipped.
•
The settings can be changed to not display.
•
When installing the unit in a place with much dusts, set the fil-
ter sign display time to shorter intervals (1,250 hours).
•
Explain it to the customer that the filter needs to be cleaned
regularly to prevent clogging and also the time that is set.
11-4 SETTINGS FOR SEPARATELY SOLD
ACCESSORIES
•
See the instruction manuals included with separately sold
accessories for the necessary settings.
When using a wireless remote controller
•
A wireless remote controller address needs to be set when
using a wireless remote controller. See the installation man-
ual included with the wireless remote controller for details on
how to make the settings.
(3) Perform a test run according to the outdoor unit’s
installation manual.
•
The operation lamp of the remote controller will flash
when a malfunction occurs. Check the malfunction code
on the liquid crystal display to identify the point of trouble.
An explanation of malfunction codes and the correspond-
ing trouble is provided in “CAUTION FOR SERVICING”
of the outdoor unit.
If the display shows any of the following, there is a possi-
bility that the wiring was done incorrectly or that the
power is not on, so check again.
CAUTION
•
Always stop the test run using the remote controller to stop
operation.
(4) After finishing the test run, make sure to check drain-
age in the drain pump according to “7. DRAIN PIPING
WORK”.
External static
pressure
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Standard
(10Pa)
13(23)
5
01
High static pres-
sure setting
(30Pa)
02
External ON/OFF input
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Forced off
12(22)
1
01
ON/OFF operation
02
Forced off
ON/OFF operation
Input A “on” to force a stop
(remote controller reception prohibited)
Unit operated by changing input A from
“off” to “on”
Input A “off” to allow remote controller
Unit stopped by changing input A from “on”
to “off”
SETTING
Mode No.
SECOND
CODE NO.
FIELD SET
MODE
FIRST
CODE NO.
Mode No.
FIRST CODE NO.
SECOND
CODE NO.
01
02
10 (20)
0
Filter dirt
low
high
1 (low/high)
Displayed time
(units: hours)
2500/
1250
10000/
5000
3
Filter sign
display
ON
OFF
Remote control display
Content
“
” display
• There is a short circuit at the FORCED
OFF terminals (T
1
, T
2
).
“
” display
• The test-run has not been performed.
“
” display
“
” display
• The power on the outdoor unit is off.
• The outdoor unit has not been wired for
power supply.
• Wiring is incorrect for the transmission
wiring and / or FORCED OFF wiring.
• The transmission wiring is cut.
“
” display
• Reversed transmission wiring
No display
• The power on the indoor unit is off.
• The indoor unit has not been wired for
power supply.
• Wiring is incorrect for the remote con-
troller wiring, the transmission wiring
and / or the FORCED OFF wiring.
• The remote controller wiring is cut.
4PEN325876-1F.book Page 13 Thursday, April 20, 2017 8:20 AM