10
|
Maintenance and service
Installer and user reference guide
36
FXHA32~100AVEB
VRV system air conditioner
4P673749-1 – 2022.01
10.4 Maintenance after a long stop period
E.g., at the beginning of the season.
▪
Check and remove everything that might be blocking inlet and outlet vents of
indoor units and outdoor units.
▪
Clean air filters and casings of indoor units (see
"10.2 Cleaning the unit exterior,
air filter and suction grille"
▪
Insert batteries in the user interface (if applicable).
10.5 About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent gases into the
atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Please contact your installer for more information.
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
WARNING
▪
Do NOT pierce or burn refrigerant cycle parts.
▪
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
▪
Be aware that the refrigerant inside the system is odourless.
WARNING
▪
The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If
the refrigerant leaks in the room and comes in contact with fire from a burner, a
heater, or a cooker, this may result in fire, or the formation of a harmful gas.
▪
Turn OFF any combustible heating devices, ventilate the room, and contact the
dealer where you purchased the unit.
▪
Do NOT use the unit until a service person confirms that the part from which the
refrigerant leaked has been repaired.