Capacity Tables
EDUS39-900-F10
10
FXMQ-MF
FXMQ72MFVJU
Coolin
g
Heatin
g
Notes
:
1. The above capacities are based on the follo
w
ing conditions:
Air discharge temperature setting: 64°F for cooling operation,
77°F for heating (Factory setting).
Equivalent piping length: 25ft.
Level difference: 0ft.
2. The above capacities values are general average values
w
hich can be generated by each compressor operation level.
3. A value enclosed in
means rated capacity.
Outdoor air temp
FWB
FDB
62
66
70
74
78
82
86
90
capacity
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
67
19600
24000
-
-
-
-
-
-
71
19600
24000
27600
-
-
-
-
-
75
19600
24000
27600
34700
-
-
-
-
79
-
24000
27300
34400
-
-
-
-
83
-
-
27300
34000
56500
-
-
-
87
-
-
27000
33700
55900
72600
-
-
91
-
-
27000
33100
55600
72000
84200
-
95
-
-
-
32700
54900
71300
83800
89300
Outdoor air temp
FWB
FDB
19
23
27
31
35
39
43
51
55
capacity
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
Btu/h
22
50700
50700
-
-
-
-
-
-
-
32
-
-
47000
-
-
-
-
-
-
37
-
-
41200
41200
41200
-
-
-
-
42
-
-
-
-
33800
33800
33800
-
-
52
-
-
-
-
-
26300
26300
26300
-
57
-
-
-
-
-
-
18900
18900
18900
Summary of Contents for FXMQ-MF
Page 1: ...EDUS 39 900 F10_a AMERICAS FXMQ MF Outdoor Air Processing Unit ...
Page 7: ...Dimensions EDUS39 900 F10 6 FXMQ MF FXMQ72MFVJU FXMQ96MFVJU Unit in 3D065453A ...
Page 8: ...EDUS39 900 F10 Piping Diagrams FXMQ MF 7 4 Piping Diagrams 4D018650C ...
Page 17: ...Fan Performances EDUS39 900 F10 16 FXMQ MF FXMQ96MFVJU 3D065651B ...
Page 19: ...Sound Levels Reference EDUS39 900 F10 18 FXMQ MF FXMQ96MFVJU 4D068577 ...