Installation
EDUS39-900-F10
32
FXMQ-MF
DB: Dry Bulb Temperature
Note:
The FA
N
OPERATIO
N
mode is set automatically for DB temperature of 59ºF and above.
If the temperature or the humidity is beyond these conditions, safety devices may
w
ork and the unit may not operate.
3P086156-12Y
HEATI
N
G
[°F]
OUTDOOR TEMPERATURE
DB
23 to 59 (
N
ote)
Restrictions in case of mixture connection with standard indoor units
Outdoor-air processing unit
Standard indoor unit
1. Restrictions of the refri
g
erant pipin
g
system
1) The total capacity of standard indoor units + Outdoor-air processing units should be
50-100%
of
Outdoor unit capacity. (In case of using only outdoor-air processing units, it is same.)
2) The capacity of outdoor-air processing units should be less than
30%
of the outdoor unit capacity.
2. Restrictions of the control system
1) In case of
w
iring is mixed
w
ith standard indoor units, group control by
remote controller is not available, because the setting temperature
are different.
3) Don't set the R/C of Outdoor-air processing unit as the master remote controller.
2) When using the central remote controller, mixture of indoor units & Outdoor-air Processing
units in the same zone is not available, because the setting temperature are different.
Set one of these remote controllers as the master remote controller.
ZO
N
E1
ZO
N
E2
ZO
N
E3
ZO
N
E1
ZO
N
E2
Summary of Contents for FXMQ-MF
Page 1: ...EDUS 39 900 F10_a AMERICAS FXMQ MF Outdoor Air Processing Unit ...
Page 7: ...Dimensions EDUS39 900 F10 6 FXMQ MF FXMQ72MFVJU FXMQ96MFVJU Unit in 3D065453A ...
Page 8: ...EDUS39 900 F10 Piping Diagrams FXMQ MF 7 4 Piping Diagrams 4D018650C ...
Page 17: ...Fan Performances EDUS39 900 F10 16 FXMQ MF FXMQ96MFVJU 3D065651B ...
Page 19: ...Sound Levels Reference EDUS39 900 F10 18 FXMQ MF FXMQ96MFVJU 4D068577 ...