Features
EDUS39-900-F10
2
FXMQ-MF
1. Features
Combine fresh air treatment
and air conditioning,
supplied from a single system.
Outdoor-Air Processing Unit
FXMQ4
8
MFVJU, FXMQ72MFVJU,
FXMQ96MFVJU
Model Names
Fresh air treatment and air conditioning
can
b
e achie
v
ed with
a single system
b
y
u
sing heat p
u
mp
technology—witho
u
t the
u
s
u
al
tro
ub
lesome air s
u
pply and air
discharge
b
alance design. Fan coil
u
nits for air conditioning and
an o
u
tdoor-air processing
u
nit can
b
e
connected to the same refrigerant line.
The res
u
lts are enhanced design
flexi
b
ility and a significant red
u
ction in
total system costs.
Combination with VRV
O
u
tdoor-Air Processing Unit
Indoor Unit
Indoor Unit
VRV Series
O
u
tdoor Units
Air
Conditioning
Outdoor
Air Supply
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
Connection Conditions
•
W
hen o
u
tdoor-air processing
u
nits are connected, the total connection capacity m
u
st
b
e within 50% to 100% of that of the o
u
tdoor
u
nits.
•
W
hen o
u
tdoor-air processing
u
nits and standard indoor
u
nits are connected, the total connection capacity of the o
u
tdoor-air processing
u
nits m
u
st not exceed 30% of that of the
o
u
tdoor
u
nits.
• O
u
tdoor-air processing
u
nits can
b
e
u
sed witho
u
t indoor
u
nits.
• Connecta
b
le o
u
tdoor
u
nits: R-410A P series.
60 Hz only
For outdoor units of 8 HP and above
Air conditioning and outdoor air processing can be accomplished using a single system.
Summary of Contents for FXMQ-MF
Page 1: ...EDUS 39 900 F10_a AMERICAS FXMQ MF Outdoor Air Processing Unit ...
Page 7: ...Dimensions EDUS39 900 F10 6 FXMQ MF FXMQ72MFVJU FXMQ96MFVJU Unit in 3D065453A ...
Page 8: ...EDUS39 900 F10 Piping Diagrams FXMQ MF 7 4 Piping Diagrams 4D018650C ...
Page 17: ...Fan Performances EDUS39 900 F10 16 FXMQ MF FXMQ96MFVJU 3D065651B ...
Page 19: ...Sound Levels Reference EDUS39 900 F10 18 FXMQ MF FXMQ96MFVJU 4D068577 ...