background image

English 

8

To keep the piping from becoming clogged with dirt, 

• 

avoid bends where possible and install so that traps can 
be cleaned.

At least 
4 in.

Air handler

At least 
3 in.

Fig. 7

Observe the following guidelines when installing con-

• 

centrated drain piping. Select the thickness of the 
concentrated drain piping to refl ect the capacity of the 
machine to which it will be connected. (Install a drain 
trap for each indoor unit.) (

Refer to Fig. 8

)

At least 4 in.

Fig. 8

Concentrated drain piping
(Use a downward slope of at least 1/100.)

 CAUTION

Water accumulating in the drain piping can cause the drain 

 

to clog.

PRECAUTIONS

Drain piping connections

Do not connect the drain piping directly to sewage piping 

• 

that smell of ammonia. The ammonia in the sewage might 
enter the indoor unit through the drain piping and corrode 
the heat exchanger.
Do not twist or bend the drain hose, as excessive force may 

• 

cause it to leak.

After piping work is fi nished, check drainage fl ows 

(2) 

smoothly.

Gradually insert approximately 1 quart of water into the 

• 

drain pan to check drainage in the manner described 
below.

INSTALLING THE  DUCT

7. 

Exercise care regarding the following when performing duct 
work.

Verify that duct work does not exceed the unit’s setting range 

• 

of external static pressure (up to 0.5 Wg at “H” speed).
Install canvas ducts at air outlets and inlets so that vibrations 

• 

from the main unit are not transmitted to ducts or the fl oor. 
Additionally, line the duct with sound-absorbing material 
(heat insulation material) as necessary.
Be sure to install a optional air fi lter to the product’s air inlet 

• 

or to a fi eld-supplied air inlet inside the air passage on the 
suction side.
Perform the curing and other work during duct welding so 

• 

that the inside of the product is not exposed to spatter.

If the metal duct passes through a metal lath, wire lath, or 

• 

metal plate of a wooden structure, isolate the duct from the 
wall electrically.
Be sure to heat-insulate the duct to prevent the formation of 

• 

condensation. (Material: Glass wool or polyethylene foam; 
thickness: 1 inch.)
Explain to the customer how to operate and clean fi eld-

• 

supplied components such as air fi lters, air inlet grilles, air 
outlet grilles.
To prevent drafts, locate the air outlet grille on the indoor 

• 

side so that warm air from the outlet does not come into 
direct contact with room occupants.
When an electric heater (optional) is installed, use metal 

• 

duct and wrap the duct with a glass-wool insulation material.

ELECTRIC WIRING WORK

8. 

GENERAL INSTRUCTIONS

8-1 

Shut off the power before doing any work.

• 

All fi eld supplied parts and materials, electric works must 

• 

conform to local codes.
Use copper wire only.

• 

See also the “Wiring Diagram Label” located inside the unit’s 

• 

fan housing.
For details on hooking up the remote controller, refer to the 

• 

“REMOTE CONTROLLER INSTALLATION MANUAL”
All wiring must be performed by an authorized electrician.

• 

This system consists of multiple indoor units. Mark each 

• 

indoor unit as unit A, unit B . . . , and be sure the terminal 
board wiring to the outdoor unit and Branch Selector unit are 
properly matched. If wiring and piping between the outdoor 
unit and an indoor unit are mismatched, the system may 
cause a malfunction.
Install a wiring interrupter or ground-fault circuit interrupter 

• 

for the power wiring.
Make sure the ground resistance is no greater than 100

• 

Ω

.

To avoid short circuiting the power supply wire, be sure to 

• 

use insulated terminals.
Do not turn on the power supply (wiring interrupter or 

• 

ground-fault circuit interrupter) until all other work is done.

 DANGER

Do not ground units to water piping, telephone wires or 

 

lightning rods because incomplete grounding could cause a 
severe shock hazard resulting in severe injury or death, nor 
to gas piping because a gas leak could result in an explo-
sion which could lead to severe injury or death.

LIST OF STANDARD WIRING EQUIPMENT

8-2 

Power supply wiring

(including ground wire)

Transmission wiring

Remote controller wiring

Field fuses 

Size

Wire

Size

15A

Must comply 

with local 

codes.

2-conductor, 

stranded, non-

shielded copper/

PVC or vinyl jacket

AWG18 – 16

Summary of Contents for FXTQ12PAVJU

Page 1: ...manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f r...

Page 2: ...the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due to risk of explosions that can cause serious injury or death Safely dis...

Page 3: ...ince R 410A is a blend the required additional refriger ant must be charged in its liquid state If the refrigerant is charged in a state of gas its composition can change and the system will not work...

Page 4: ...FINISHED a Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor units fixed firmly The units may drop vibrate...

Page 5: ...door and outdoor units power supply wiring and connecting wires at least 3 5 ft away from televi sions or radios in order to prevent image interference or noise Depending on the radio waves a distance...

Page 6: ...ontally level 4 CAUTION Make sure the unit is installed level using a level tube four sides One thing to watch out for in particular is if the unit is installed so that the slope is not in the directi...

Page 7: ...The outdoor unit is charged with refrigerant This coil contains gas under 150 P S I G Release pressure from the gas piping pressure release device before initiating piping work Detail Cap After the w...

Page 8: ...refrigerant piping systems For instance if chlorine based flux is used it will cause piping corrosion Flux containing fluorine will damage refrigerant oil DRAIN PIPING WORK 6 CAUTION Make sure all wat...

Page 9: ...he duct to prevent the formation of condensation Material Glass wool or polyethylene foam thickness 1 inch Explain to the customer how to operate and clean field supplied components such as air filter...

Page 10: ...sides as shown in the figure Electric wire Round crimp style terminal Insulation sleeve Connect wires of the same gauge to both sides Do not connect wires of the same gauge to one side Do not connect...

Page 11: ...er supply wiring and the ground wire 5 through the conduit conduit should be field sup plied The hole for running wires through should be sealed completely to prevent air from entering When installing...

Page 12: ...oup control It is automatically set when the power is turned on Indoor unit A Indoor unit B Most down stream indoor unit For use with 2 remote controllers Case of group control L1L2 Remote controller...

Page 13: ...IELD SETTING AND TEST RUN 10 Field settings may have to be performed using the re mote controller depending on the type of installation Make sure the electric component box covers are 1 closed on the...

Page 14: ...ff the part on the bottom of the front panel 1 Insert the air filter as far as it can go 2 Air filter optional accessories INSTALLATION OF THE ELECTRIC HEATER KIT 10 5 WARNING All phases of the electr...

Page 15: ...e blower deck The HKR 03 and HKR 06 have no circuit breaker mount ing bracket Procure and install a circuit breaker Connect the relay connector of the heater kit to the relay 6 connector of the produc...

Page 16: ...th Open the knock hole of the plastic cover provided for 10 the front panel upper so that the circuit breaker will be turned on and off through the hole This step is not required for HKR 03 and HKR 06...

Page 17: ...air 1 purifier UV lamp Humidifier economizer and air purifier UV lamp are sold separately For the method of installation refer to the manual provided with each optional product WARNING If the unit is...

Page 18: ...any of the following there is a possibility that the wiring was done incorrectly or that the power is not on so check again Remote control display Content display There is a short circuit at the FORCE...

Page 19: ...3P250363 2B EM09A034A 1011 FS...

Reviews: