English
14
3.
Gradually pour 1 liter of water from the air outlet
into the drain pan (
Fig. 34
) giving caution to avoid
splashing water on the electric components such as
drain pump.
If the air outlet
is closed, pour water from the air
outlet .
4.
When the power supply is turned on, the drain pump
will operate. Check drainage.
(The drain pump will automatically stop after 10 min-
utes.)
5.
Turn off the power supply after checking drainage,
and remove the power supply wiring.
6.
Attach the control box lid as before.
8.
ELECTRIC WIRING WORK
8-1 GENERAL INSTRUCTIONS
•
Make certain that all electric wiring work is carried out by
qualified personnel according to the applicable legislation
and this installation manual, using a separate dedicated cir-
cuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or a fire.
•
Make sure to install an earth leakage breaker.
Failure to do so may cause electrical shocks and a fire.
•
Do not turn on the power supply (branch switch, branch over-
current breaker) until all the works are finished.
•
Multiple number of indoor unit are connected to one outdoor
unit. Name each indoor unit as A-unit, B-unit ….. and the like.
When these indoor units are wired to the outdoor unit and the
BS unit, always wiring the indoor unit to the terminal indi-
cated with the same symbol on the terminal block. If the wir-
ing and the piping are connected to the different indoor units
and operated, it will result in malfunction.
•
Make sure to earth the air conditioner. Earthing resistance
should be according to applicable legislation.
•
Do not connect the earth wiring to gas or water piping, light-
ning conductor or telephone earth wiring.
• Gas piping ............ Ignition or explosion may occur if the
gas leaks.
• Water piping ......... Hard vinyl tubes are not effective
earths.
• Lightning conductor or telephone earth wiring .................
............................. Electric potential may rise abnormally
if struck by a lightning bolt.
•
For electric wiring work, refer to also the “WIRING DIA-
GRAM” attached to the control box lid.
•
Carry out wiring between the outdoor units, indoor units and
the remote controllers according to the wiring diagram.
•
Carry out installation and wiring of the remote controller
according to the “installation manual” attached to the remote
controller.
•
Do not touch the Printed Circuit Board assembly. It may
cause malfunction.
8-2 ELECTRICAL CHARACTERISTICS
MCA: Min. Circuit Amps (A) ;
MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)
8-3 SPECIFICATION FOR FIELD SUPPLIED FUSES
AND WIRING
The lengths of remote controller wiring and transmission wiring
are as follows:
(1) Remote controller wiring (indoor unit - remote controller)....
.......................................................Max. 500m
(2) Transmission wiring ........... Total wiring length 2000m
• Outdoor unit - Indoor unit ........... Max. 1000m
• Outdoor unit - BS unit................. Max. 1000m
• BS unit - Indoor unit.................... Max. 1000m
• Indoor unit - Indoor unit .............. Max. 1000m
NOTE
1.
Shows only in case of protected piping. Use H07RN-F in
case of no protection.
2.
Vinyl cord with sheath or cable (Insulated thickness : 1mm
or more)
8-4 WIRING CONNECTION METHOD
(Refer to Fig. 38)
CAUTION FOR WIRING
• The indoor units in the same system can be connected to the
power supply from one branch switch.
However, selection of branch switch, branch over current breaker
and wiring size must be according to applicable legislation.
• For connection to the terminal block, use ring type crimp
style terminals with insulation sleeve or treat the wiring
with insulation.
(Refer to Fig. 36)
• If the above is not available, make sure to observe the fol-
lowing items.
(Abnormal heating may occur if the wiring are not tight-
ened securely.)
• Use the required wiring, connect them securely and fix these
wiring so that external force may not apply to the terminals.
• Use a proper screw driver for tightening the terminal screws.
If an improper screw driver is used, it may damage the
screw head and a proper tightening cannot be carried out.
Indoor units
Power supply
Fan motor
Model
Hz
Volts
Voltage
range
MCA
MFA
kW
FLA
FXUQ71AVEB
50
60
220-240
220·230
Max. 264
Min. 198
0.6
16
0.046
0.5
FXUQ100AVEB
1.4
16
0.106
1.1
3
3
2
Model
Power supply wiring
Remote controller
wiring
Transmission wiring
Field
fuses
Wiring
Size
Wiring
Size
FXUQ71AVEB
16A
H05VV-
U3G
NOTE 1)
Wiring
size and
length
must
comply
with local
codes.
Vinyl
cord with
sheath or
cable
(2 core)
NOTE 2)
0.75 -
1.25mm
2
FXUQ100AVEB
Insulation sleeve
Ring type crimp style terminal
Wiring
Fig. 36
Connection of 2
wirings of same
size must be
carried out on both
sides.
Connection of 2
wirings on one side
is prohibited.
Connection of
wiring of different
sizes is prohibited.
Fig. 37
01_EN_3P177351-7S.fm Page 14 Thursday, March 21, 2013 10:19 PM