SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
151
3.29
Malfunction of Transmission Between Outdoor Units
Remote Controller
Display
U7
Supposed Causes
Improper connection of transmission wiring between outdoor unit and outdoor unit outside control
adaptor
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of outdoor unit outside control adaptor
Troubleshooting
(VF056)
NO
YES
Fix the indoor/outdoor unit
transmission wiring.
Replace the outdoor unit PC
Board (A1P).
YES
NO
C/H SELECT is set to "IND".
Cool / heat selection is unified.
C/H SELECT
is set to "MASTER."
NO
Is the indoor
/ outdoor unit transmission
wiring normal?
C/H SELECT
is set to "SLAVE."
YES
NO
Check
and see if the following items
are normal.
NO
Does
a malfunction occur when
the cool / heat selector is set
to "IND?"
YES
Set C/H SELECT to "IND."
The cool / heat unified address for
outdoor units in outdoor - outdoor
unit transmission is duplicated.
Set the address correctly.
YES
NO
NO
YES
YES
Replace the outdoor unit outside
control adaptor. replacement
Replace the outdoor unit PC
board (A1P).
Outdoor unit outside control adaptor
•
Is there continuity?
•
Does the cool/heat unified address match?
Outdoor unit (unified master unit)
•
Is there continuity?
•
Does the cool/heat unified address match?
Fix the problem.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...