SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
155
3.33
Address Duplication of Central Remote Controller
Remote Controller
Display
UC
Supposed Causes
Address duplication of central remote controller
Defect of indoor unit PC board
Troubleshooting
3.34
Refrigerant System not Set, Incompatible Wiring/Piping
Remote Controller
Display
UF
Supposed Causes
Improper connection of transmission wiring between outdoor unit and outdoor unit outside control
adaptor
Failure to execute wiring check operation
Defect of indoor unit PC board
Troubleshooting
Wiring check may not be successful if carried out after the outdoor unit has been off for more than 12
hours, or if it is not carried out after running all connected indoor units in the fan mode for at least an hour.
(VF060)
Replace indoor unit PC board.
Address duplication of central remote
controller
The setting must be changed so that
the central remote control address is
not duplicated.
YES
NO
Optional
controllers for
centralized control are
connected to the
indoor unit.
(VF061)
Is indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
Replace indoor unit PC board.
Wiring check may not have been
carried out successfully.
After fixing incorrect wiring, push
and hold the RESET button on the
outdoor unit PC board for 5
seconds.
YES
NO
YES
NO
NO
YES
Wiring
check operation
carried out?
Is indoor
-outdoor and outdoor-outdoor
unit transmission
wiring normal?
∗
The unit will not run for up to 12
minutes.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...