Outline of Control (Outdoor Unit)
SiE 00-07
60
Function R-407C PLUS Series
[Oil return mode (common for cooling / heating)]
Outdoor unit fan and hot gas bypass solenoid valve (SVP) under oil return operation are controlled not to
actuate high pressure protection. Also outdoor fan is controlled to protect short refrigerant circulation due to
low high pressure during low ambient temperature. ( Oil returning is hard at short refrigerant circulation)
Soft star
tup
Defrost / Oil retur
n
Nor
mal control
Condition
(2)
Condition
(4)
Condition
(1)
Condition
(3)
Step1
Step2
Step3
Step4
Hz
Fan
SVP
SVS
EV
SVT
EV
Indoor unit control
(Command from outdoor unit)
Outdoor unit control
33Hz
+OFF
OFF
Normal
control
Thermostat ON · · · 2000pls
Thermostat OFF · · · 224pls
Non-operation unit · · · 224pls
Thermostat ON · · · Normal control
Thermostat OFF · · · 224pls
Non-operation unit · · · 224pls
Thermostat ON · · · Normal control
Thermostat OFF · · · 224pls
Non-operation unit · · · 224pls
Thermostat ON · · · Normal control
Thermostat OFF · · · Normal control
Non-operation unit · · · Normal control
PI control when
SHS = 15
PI control when
SHS = 10
PI control when
SHS = 5
PI control when
SHS = 5
Normal
control
Normal
control
Normal
control
OFF
OFF
OFF
ON
ON
ON
ON
33Hz
+OFF
33Hz
+OFF
33Hz
+OFF
Pc < 2.16 MPa (54.8 ˚C) continues for 20 sec
Pc > 2.66 MPa (63.6˚C)
Pc < 1.88 MPa (49.8˚C) continues for 20 sec
Pc < 1.72 MPa (46.4˚C) continues for 20 sec
Pc > 2.05 MPa (52.7˚C)
Pc > 2.15 MPa (57.0˚C)
Forced thermostat
OFF
Malfunction stop
Up to 2 times within 30 min
3.09 MPa
2.81 MPa
(V0824)
SVP : ON
Fan : Step
HP<1.72MPa
HP>2.16MPa
SVP : OFF
Fan : Step
HP<1.49MPa
HP>1.79MPa
SVP : OFF
Fan : Step
(V0825)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...