Troubleshooting
SiE 00-07
136
Troubleshooting R-407C PLUS Series
3.12
Indoor Unit: Malfunction of Thermostat Sensor in Remote Controller
Remote Controller
Display
CJ
Supposed Causes
Defect of remote controller thermistor
Defect of remote controller PC board
Troubleshooting
3.13
Outdoor Unit: Actuation of Safety Device
Remote Controller
Display
E0
Supposed Causes
Actuation of outdoor unit safety device
Defect of outdoor unit PC board
Instantaneous power failure
Troubleshooting
∗
1: Actuation of magnet switch OC
Defect of compressor
Power supply insufficient
Defect of magnet switch, etc.
∗
2: Actuation of fan motor safety thermostat
Defect of fan motor
Defect of capacitor, etc.
Turn power supply OFF, then
power ON again.
Is "CJ" displayed on the
remote controller?
YES
Replace remote controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
(VF039)
NO
(VF040)
Connector
or terminal is
connected to X8A - X9A of
the outdoor unit PC board
(A1P) and
X1S - X2S.
Contacts
F2C (X1S - X2S) are open.
Connect the connector or terminal and
turn on again.
Actuation of magnet switch
OC for standard compressor.
∗
1
Actuation of fan motor safety
thermostat.
∗
2
YES
NO
NO
YES
Contact
Q1M (X8A) or Q2M (X9A)
is open.
NO
YES
Operation
is normal when turned on
again by remote
controller.
YES
NO
Replace outdoor unit PC board A1P.
There was an instantaneous power
failure or a past safety device actuated.
Re-check refrigerant system.
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...