EWLP012~065KAW1N

Condenserless water-cooled water chillers

4PW30043-1

Operation manual

8

Resetting warnings

During normal operation, the display of the controller may start
flashing, alternately showing the inlet water temperature and the
following warning code:

n1

: indicates that the compressor1 requires maintenance: the

total running hours of the compressor1 (direct parameter 

c9

)

has exceeded the setting of the timer threshold for
maintenance warning (user parameter 

cb

).

n2

: indicates that the compressor2 requires maintenance: the

total running hours of the compressor2 (direct parameter 

ca

)

has exceeded the setting of the timer threshold for
maintenance warning (user parameter 

cb

).

To reset the maintenance warning 

n1

 or 

n2

, proceed as follows:

1

Enter the list of direct parameters by pressing the 

R

  key for

approximately 5 seconds.

The parameter code 

r1

 appears on the display.

2

Select parameter code 

c9

 or 

ca

 using the 

A

 and/or 

Z

 key.

3

Press the 

R

 key to switch to the parameter value.

4

Press the 

A

  and 

Z

  keys simultaneously for approximately

5 seconds.

The timer's value becomes 

0

5

Press the 

R

 key to return to parameter code 

c9

 or 

ca

.

6

Press the 

E

 key to return to normal operation.

Advanced features of the digital controller

This chapter gives an overview of the direct parameters and user
parameters provided by the controller. In the following chapter, you
will learn how you can set up and configure the EWLP unit using
these parameters.

Overview of the direct parameters

The list of direct parameters is accessible by pressing the 

R

 key for

approximately 5 seconds.

When scrolling through the list of direct parameters using the 

A

 and/

or 

Z

 key, the parameters appear in the following order:

r1

: to define the cooling temperature setpoint,

r2

: to define the cooling temperature difference,

r6

: to check the evaporator outlet water temperature,

r8

: to check the ambient temperature

c9

: to check the total running hours of the compressor1,

ca

: to check the total running hours of the compressor2,

cv

: to check the total running hours of the pump.

Overview of the user parameters

The list of user parameters is only accessible by means of the user
password. When scrolling through the list of parameters using the 

A

and/or 

Z

 key, you see the direct parameters and user parameters.

The user parameters appear in the following order:

:d

: to define the measurement unit (°C or °F),

c7

: to define the time delay between the pump startup and the

compressor startup,

c8

: to define the time delay between the unit shutdown and the

pump shutdown,

cb

: to define the time threshold for maintenance warning,

p4

: to disable the buzzer or to define the activation period of the

buzzer in case of an alarm,

h7

: to activate or de-activate the remote on/off control,

h9

: to lock or unlock the controller keyboard,

ha

: to define the unit's serial address,

h8

,

hb

,

c6

: not used.

Tasks carried out using direct parameters

Entering the list of direct parameters

1

Press the 

R

 key for approximately 5 seconds.

The controller enters the list of direct parameters, displaying
parameter code 

r1

.

Defining the cooling temperature difference

To  control the cooling load, the unit with 1 compressor is equipped
with a single-step thermostat. The unit with 2 compressors is
equipped with a two-step thermostat.  The thermostat's "cooling
temperature difference" can be modified by means of direct
parameter 

r2

.

The default, limit and step values are: 

Default value

3

.

0

°C

Limit values

0

.

3

 to 

19

.

9

°C

Step value

0

.

1

°C

To define the cooling temperature difference, proceed as follows:

1

Enter the list of direct parameters.

2

Press the 

A

 key once.

Direct parameter code 

r2

 appears on the display.

3

Press the 

R

 key to switch to the parameter value.

4

Select the appropriate setting using the 

A

 and/or 

Z

 key.

5

Press the 

R

 key to switch to the list of parameter codes.

6

To adjust or to consult other direct parameters before saving the
modifications, select another direct parameter using the 

A

 and/

or 

Z

 key and then repeat from instruction 3 onwards.

NOTE

Do not forget to carry out the required maintenance
activities after resetting the timers.

Besides resetting timer 

c9

  (running hours of the

compressor 1)  and 

ca

  (running hours of the

compressor 2), it is also possible to reset timer 

cv

which defines the total running hours of the pump. To
do this, consult the timer's value (refer to paragraph

"Consulting actual operational information" on page 7

)

and press the 

A

  and 

Z

  keys simultaneously for

approximately 5 seconds while the timer's value is
displayed. The timer's value becomes 

0

.  Then

successively press the 

R

 key and the 

E

 key to return

to normal operation.

for 1 compressor

for 2 compressors

12

15

 compressor

 inlet

 water

 temperature

 of evaporator

 ON

 OFF

12

15

13.5

 compressor(s)

 inlet

 water

 temperature

 of evaporator

 ON

 ON

 OFF

 OFF

 compressor2

 compressor1

Summary of Contents for Hydrocube EWLP012KAW1N

Page 1: ...OPERATION MANUAL EWLP012KAW1N EWLP020KAW1N EWLP026KAW1N EWLP030KAW1N EWLP040KAW1N EWLP055KAW1N EWLP065KAW1N Condenserless water cooled water chillers...

Page 2: ...THROW THIS MANUAL AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE Read the chapter Overview of the user parameters on page 8 before changing the parameters Before starting up the unit for the first t...

Page 3: ...Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current A 11 6 14 7 16 8 Control Phase 1 Frequency Hz...

Page 4: ...I O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected...

Page 5: ...ut having to drain the water circuit Water filter delivered with the unit installed in the field The filter installed in front of the unit removes dirt from the water to prevent damage to the unit or...

Page 6: ...Switch on the circuit breaker on the unit Make sure that the unit is OFF on the controller 2 The crankcase heater is switched on automatically 3 Check the supply voltage on the supply terminals L1 L2...

Page 7: ...also be caused by an overcharge of refrigerant Working pressure It is important to check the high and low pressure of the refrigerant circuit to ensure the proper operation of the unit and to guarant...

Page 8: ...normal operation displaying the inlet water temperature In the second case the display will start flashing Approximately 40 seconds later the controller leaves the list of direct para meters The inlet...

Page 9: ...appear in the following order d to define the measurement unit C or F c7 to define the time delay between the pump startup and the compressor startup c8 to define the time delay between the unit shut...

Page 10: ...e delay between pump and compressor startup User parameter c7 allows you to define the time delay between the pump startup and the compressor startup The default limit and step values for the time del...

Page 11: ...eration displaying the inlet water temperature In the second case the display starts flashing Approximately 40 seconds later the controller leaves the list of user parameters without saving the modifi...

Page 12: ...start but the T LED is flashing Symptom 3 The unit does not start and the T LED does not light up Symptom 4 One of the following safety devices is activated When carrying out an inspection on the sup...

Page 13: ...the fans turn freely Clean if necessary Dirty or partially blocked condenser Remove any obstacle and clean condenser coil using brush and blower Inlet air temperature of the condenser is too high The...

Page 14: ...he figures below represent the average saturated temperature of R407C in relation to the pressure readout High pressure side Low pressure side conditions high pressure 20 bar subcool 3 C NOTES 10 20 1...