background image

IM 1093-1 • SINGLE DUCT VAV TERMINALS 4 

www.DaikinApplied.com

I

nsTallaTIon

 

I

nsTallaTIon

 

Receiving Inspection

Prior to removing the shipping material, visually inspect the 

packing materials. There should be a black plastic strip wrapped 

in the clear plastic shrink wrap. If this black plastic strip is 

missing, the shipment may have been repacked by the shipper 

and you should make note of this on the shipping documents 

and inform the delivering carrier. After unpacking the terminal, 

check it for shipping damage. If any shipping damage is found, 

report it immediately to the delivering carrier. Store units in a 

clean, dry location prior to installation. Units with controls are 

not recommended for use in ambient temperatures greater 

than 95°F. For protection of controls, do not store in ambient 

temperatures greater than 135°F. Caution: Do not use the 

flow sensor, connecting tubing, or damper shaft as a lift point. 

Damage to the flow sensor or controls may result.  

Hanging/Installation Requirements

 IMPORTANT

If  equipped  with  pneumatic  controls,  the  orientation  of  the 

terminal is critical. The pneumatic controls must be mounted 

right side up. The single duct unit must be level  or – 

10 degrees of horizontal, both parallel to the air flow and at 

the right angle of air flow. The control side of the terminal is 

labeled with an arrow indicating UP. Unless otherwise noted, 

most  analog  and  digital  controls  may  be  installed  in  any 

orientation. Check with the local Daikin representative for 

verification.

 CAUTION

Cautions indicate potentially hazardous situations, which 

can result in personal injury or equipment damage if not 

avoided . 

The  equipment  is  heavy  and  counted  in  the  ceiling.  Use 

caution and follow OSHA and SMACNA installation guidelines. 

Unless local building codes require hangers, the smaller 

size basic single duct terminals may be light enough to be 

supported by the ductwork itself. However, when accessory 

modules, such as DDC controls, hot water coils, or sound 

attenuators are included, the single duct terminal should be 

supported directly. Straps screwed directly into the side of the 

terminal, trapeze hangers, or the method prescribed for the 

rectangular duct on the job specifications may be used (See 

Figure 1

 and 

Figure 2

). The MQTHI5 Single Duct Terminal is 

not suitable for outdoor use. 

Figure 1: Strap-Hangers     

Summary of Contents for IM 1093-1

Page 1: ...Installation and Maintenance Manual IM 1093 1 Group Controls Part Number IM 1093 Date February 2015 Single Duct VAV Terminals...

Page 2: ...on 4 Hanging Installation Requirements 4 Minimum Clearance for Access 5 Connecting Ductwork 5 Field Electrical Wiring 5 MQTHI5 Single Duct Terminal Units with Electric Heat 6 MQTHI5 Single Duct Termin...

Page 3: ...rosoft Corporation Maverick RoofPak and Daikin from Daikin Applied Hazard Identification Messages DANGER Dangers indicate a definate hazardous situation physical or electrical which will result in dea...

Page 4: ...he terminal is critical The pneumatic controls must be mounted right side up The single duct unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle...

Page 5: ...sor is installed it is recommended that the installer provide three to five diameters of straight duct at the terminal inlet The outlet end of the terminal is designed for use with slip and drive duct...

Page 6: ...unication addresses Installing the terminal in a different location than noted on unit label and building plans may result in excessive start up labor Detailed information regarding connection start u...

Page 7: ...e Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while p...

Page 8: ...S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient sta...

Page 9: ...Troubleshooting www DaikinApplied com 9 IM 1093 1 SINGLE DUCT VAV TERMINALS Figure 3 MI Flow Sensor Calibration Chart...

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representativ...

Reviews: