background image

I

nsTallaTIon

 

www.DaikinApplied.com 

IM 1093-1 • SINGLE DUCT VAV TERMINALS

Figure 2: Trapeze-Hangers       

Minimum Clearance for Access

Single Duct Air Terminals require sufficient to allow servicing 

of the actuator, controls and single electric power hook-

up (if applicable). Horizontal clearance requirements are 

dependent upon access panel dimensions which are 

indicated on the appropriate submittals (for control panel 

enclosure access a minimum of 18" is recommended. See the 

appropriate submittal for control panel location). NOTE: These 

clearance recommendations are not meant to preclude NEC 

requirements or local building codes.  

Connecting Ductwork

Slip each inlet duct over the inlet collar of the terminal. Fasten 

and seal the connection by the method prescribed by the job 

specification. The diameter of the inlet duct “D” in inches must 

be equal to the listed size of the terminal; e.g. a duct that 

actually measures 8 inches must be fitted to a size 8 terminal. 

The inlet collar of the terminal is made 1/8 inch smaller than 

listed size in order to fit inside the duct. 

NOTE: 

Do not insert duct work inside the inlet collar of the 

assembly. 

Inlet duct should be installed in accordance with SMACNA 

guidelines. If a single point electronic velocity sensor is 

installed, it is recommended that the installer provide three to 

five diameters of straight duct at the terminal inlet. The outlet 

end of the terminal is designed for use with slip and drive duct 

connections (flanged outlets optional). A rectangular duct the 

size of the terminal outlet should be attached. 

Field Electrical Wiring

 

DANGER

Electric shock hazard . Can cause personal injury or 

equipment damage . 

This equipment must be properly grounded. Connections and 

service to the MicroTech III Chiller Unit Controller must be 

performed only by personnel knowledgeable in the operation 

of the equipment being controlled.

• 

All field wiring must comply with the local codes and with 

the National Electrical Code (ANSI/NFPA 70-2002). 

• 

When applicable, electrical, control and piping diagrams 

are shown on labels attached to the exterior of the single 

duct unit. 

•  Use copper conductors only! 
• 

All terminal units must be properly grounded per NEC 

424-14 and 250. 

• 

Always check product label for voltage and current data 

to determine the proper wire size and current protection. 

•  The control cabinet contains live electrical parts! 

Contacting these parts with the power applied may cause 

serious injury or death. The control cover must be closed 

prior to applying electric power to the unit. 

•  These recommendations are not meant to preclude 

NEC requirements or local building codes that may be 

applicable, which are the responsibility of the installing 

contractor. 

Summary of Contents for IM 1093-1

Page 1: ...Installation and Maintenance Manual IM 1093 1 Group Controls Part Number IM 1093 Date February 2015 Single Duct VAV Terminals...

Page 2: ...on 4 Hanging Installation Requirements 4 Minimum Clearance for Access 5 Connecting Ductwork 5 Field Electrical Wiring 5 MQTHI5 Single Duct Terminal Units with Electric Heat 6 MQTHI5 Single Duct Termin...

Page 3: ...rosoft Corporation Maverick RoofPak and Daikin from Daikin Applied Hazard Identification Messages DANGER Dangers indicate a definate hazardous situation physical or electrical which will result in dea...

Page 4: ...he terminal is critical The pneumatic controls must be mounted right side up The single duct unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle...

Page 5: ...sor is installed it is recommended that the installer provide three to five diameters of straight duct at the terminal inlet The outlet end of the terminal is designed for use with slip and drive duct...

Page 6: ...unication addresses Installing the terminal in a different location than noted on unit label and building plans may result in excessive start up labor Detailed information regarding connection start u...

Page 7: ...e Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while p...

Page 8: ...S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient sta...

Page 9: ...Troubleshooting www DaikinApplied com 9 IM 1093 1 SINGLE DUCT VAV TERMINALS Figure 3 MI Flow Sensor Calibration Chart...

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representativ...

Reviews: