IM 1093-1 • SINGLE DUCT VAV TERMINALS 6 

www.DaikinApplied.com

I

nsTallaTIon

 

MQTHI5 Single Duct Terminal Units 

with Electric Heat

 

DANGER

Electric shock hazard . Can cause personal injury or 

equipment damage . 

This equipment must be properly grounded. Connections and 

service to the MicroTech III Chiller Unit Controller must be 

performed only by personnel knowledgeable in the operation 

of the equipment being controlled. 

• 

Always inspect the electric coils for damage prior to 

installing the single duct unit. 

•  All electric heaters if provided by Daikin are balanced 

by kW per stage. The installing electrician should rotate 

these heater stages by phase in order to help balance the 

building electric load. 

• 

See above wiring instructions. 

• 

The “up” orientation must be followed. 

MQTHI5 Single Duct Terminal Units 

with Hot Water Coils

• 

Always inspect the hot water coils for damage prior to 

installing the single duct unit. 

• 

CAUTION: The copper tubing should not be used as lift 

points. 

• 

The hot water coil casing is field insulated. 

•  The hot water coils do not have a drip pan and are not 

suitable for use as cooling coils. 

Controls

 CAUTION

Static sensitive components . Can cause equipment 

damage . 

Discharge  any  static  electrical  charge  by  touching  the  bare 

metal inside the control panel before performing any service 

work. Never unplug cables, circuit board terminal blocks, or 

power plugs while power is applied to the panel. 

 IMPORTANT

Units with digital controls, if factory programmed, incorporate 

specific communication addresses. Installing the terminal in a 

different location than noted on unit label and building plans 

may result in excessive start-up labor. 

Detailed information regarding connection, start-up and 

operating procedures for controls provided by Daikin 

are available from your local Daikin representative. For 

information on controls by other manufacturers, contact that 

manufacturer’s local branch or dealer. 

Labeling

MQTHI5 Single Duct Air Terminals are shipped from the factory 

with up to seven different information labels (not all labels 

pertain to all single duct units depending upon the type of 

insulation and the final ship to state). 

1. 

Control Label – affixed to the single duct terminal casing. 

Shows piping/wiring diagram and control sequence 

number and fusing (if applicable). 

2. 

Calibration Label – affixed to the single duct terminal 

casing. Shows air flow calibration data and control 

settings (if applicable). 

3. 

I.D. Label – affixed to the single duct terminal casing. 

Shows tagging information, customer order number, ETL 

Logo, etc. 

4. 

AHRI Certification Label on Single Duct Terminal Unit – 

identifies applicable industry test standard and certifies 

unit is in compliance. 

5. 

AHRI Certification Label on Hot Water Coils – identifies 

applicable industry test standard and certifies hot water 

coil compliance (if hot water coils is ordered as an 

accessory). 

6. 

Fiberglass Label – identifies insulation type for units 

shipped to California. 

7. 

Orientation label – identifies the proper air flow direction 

and the top of the unit. 

MQTHI5 Flow Sensor

MQTHI5 Single Duct Air Terminals are shipped with a factory-

installed pressure differential flow sensor installed. See Figure 

3, for the calibration curve. 

Summary of Contents for IM 1093-1

Page 1: ...Installation and Maintenance Manual IM 1093 1 Group Controls Part Number IM 1093 Date February 2015 Single Duct VAV Terminals...

Page 2: ...on 4 Hanging Installation Requirements 4 Minimum Clearance for Access 5 Connecting Ductwork 5 Field Electrical Wiring 5 MQTHI5 Single Duct Terminal Units with Electric Heat 6 MQTHI5 Single Duct Termin...

Page 3: ...rosoft Corporation Maverick RoofPak and Daikin from Daikin Applied Hazard Identification Messages DANGER Dangers indicate a definate hazardous situation physical or electrical which will result in dea...

Page 4: ...he terminal is critical The pneumatic controls must be mounted right side up The single duct unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle...

Page 5: ...sor is installed it is recommended that the installer provide three to five diameters of straight duct at the terminal inlet The outlet end of the terminal is designed for use with slip and drive duct...

Page 6: ...unication addresses Installing the terminal in a different location than noted on unit label and building plans may result in excessive start up labor Detailed information regarding connection start u...

Page 7: ...e Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while p...

Page 8: ...S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient sta...

Page 9: ...Troubleshooting www DaikinApplied com 9 IM 1093 1 SINGLE DUCT VAV TERMINALS Figure 3 MI Flow Sensor Calibration Chart...

Page 10: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representativ...

Reviews: