background image

T

roubleshooTIng

www.DaikinApplied.com 

IM 1093-1 • SINGLE DUCT VAV TERMINALS

T

roubleshooTIng

Investigating Noise Complaints

Noise from a terminal can be due to a variety of conditions, and 

can be difficult to eliminate. The first step is to isolate the type, 

source and direction. Generally, noise heard at the air outlet is 

considered a discharge type. Noise heard through the ceiling is 

considered a radiated noise. For detailed information concerning 

noise transmission in buildings see ARI Standard 885-2008E, 

titled 

Procedure For Estimating Occupied Space Sound Levels 

In The Application Of Air Terminals and Air Outlets. 

Discharge Noise

Discharge noise is usually caused by high static or little 

to no internal duct lining downstream of the terminal. It 

can sometimes be caused by the air outlet itself. Air outlet 

generated sounds can be reduced by reducing flow or 

increasing air outlet size. Reducing static pressure, or flow, or 

adding additional attenuation materials will reduce discharge 

sounds from the terminal unit. Sometimes, moving the flex duct 

between the terminal and air outlet so the air must make an 

additional turn will help with the discharge sound.  

Radiated Noise

Radiated noise is most commonly associated with fan powered 

terminal units. 

Controls

 

DANGER

Electric shock hazard . Can cause personal injury or 

equipment damage . 

This equipment must be properly grounded. Connections and 

service to the MicroTech III Chiller Unit Controller must be 

performed only by personnel knowledgeable in the operation 

of the equipment being controlled. 

 CAUTION

Static sensitive components . Can cause equipment 

damage . 

Discharge  any  static  electrical  charge  by  touching  the  bare 

metal inside the control panel before performing any service 

work. Never unplug cables, circuit board terminal blocks, or 

power plugs while power is applied to the panel. 

Contact your Daikin representative for information concerning 

controls provided by Daikin. For controls provided by others, 

contact the local control representative for assistance. 

Electric Duct Heater

 

DANGER

Electric shock hazard . Can cause personal injury or 

equipment damage . 

This equipment must be properly grounded. Connections and 

service to the MicroTech III Chiller Unit Controller must be 

performed only by personnel knowledgeable in the operation 

of the equipment being controlled. 

• If the heater does not operate:

 

Check electric power into the unit, and verify that the

wiring agrees with the label diagram located on the 

terminal unit casing. 

 

Verify that the unit is installed properly (i.e., according 

to the air flow orientation label). Review the wiring 

diagram supplied with the heater to verify the field 

wiring is correct and of the proper gauge and that the 

heater is properly grounded. 

• If the heater cycles on and off:

 

Verify that the airflow is uniformly distributed across

the face of the heater. Check for obstructions in 

the duct, or insufficient air flow (CFM) (see label for 

minimum CFM). 

• If conditioned space fails to warm-up:

 

Make certain that the heater controls and the

thermostat are compatible and wired properly. 

Relocate the thermostat if it is located in a position 

that is too warm. 

• If conditioned space overheats:

 

Make certain that the heater controls and the

thermostat are compatible and wired properly. 

Relocate the thermostat if it is located in a position 

that is too cool. Verify that the air distribution to the 

space is appropriate for the required thermal load. 

Summary of Contents for IM 1093

Page 1: ...Installation and Maintenance Manual IM 1093 1 Group Controls Part Number IM 1093 Date February 2015 Single Duct VAV Terminals ...

Page 2: ...ion 4 Hanging Installation Requirements 4 Minimum Clearance for Access 5 Connecting Ductwork 5 Field Electrical Wiring 5 MQTHI5 Single Duct Terminal Units with Electric Heat 6 MQTHI5 Single Duct Terminal Units with Hot Water Coils 6 Controls 6 Labeling 6 MQTHI5 Flow Sensor 6 Troubleshooting 7 Investigating Noise Complaints 7 Discharge Noise 7 Radiated Noise 7 Controls 7 Electric Duct Heater 7 Spec...

Page 3: ...crosoft Corporation Maverick RoofPak and Daikin from Daikin Applied Hazard Identification Messages DANGER Dangers indicate a definate hazardous situation physical or electrical which will result in death or serious injury if not avoided WARNING Warnings indicate potentially hazardous situations which can result in property damage severe personal injury or death if not avoided CAUTION Cautions indi...

Page 4: ...the terminal is critical The pneumatic controls must be mounted right side up The single duct unit must be level within or 10 degrees of horizontal both parallel to the air flow and at the right angle of air flow The control side of the terminal is labeled with an arrow indicating UP Unless otherwise noted most analog and digital controls may be installed in any orientation Check with the local Da...

Page 5: ...nsor is installed it is recommended that the installer provide three to five diameters of straight duct at the terminal inlet The outlet end of the terminal is designed for use with slip and drive duct connections flanged outlets optional A rectangular duct the size of the terminal outlet should be attached Field Electrical Wiring DANGER Electric shock hazard Can cause personal injury or equipment...

Page 6: ...munication addresses Installing the terminal in a different location than noted on unit label and building plans may result in excessive start up labor Detailed information regarding connection start up and operating procedures for controls provided by Daikin are available from your local Daikin representative For information on controls by other manufacturers contact that manufacturer s local bra...

Page 7: ...ge Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work Never unplug cables circuit board terminal blocks or power plugs while power is applied to the panel Contact your Daikin representative for information concerning controls provided by Daikin For controls provided by others contact the local control representative for ass...

Page 8: ... S P If the available static pressure is in the dead band between these two ranges the switch will not engage and some method must be devised to increase the available static pressure If sufficient static pressure is available check to insure the pneumatic tube is connected to the correct port of the switch For negative pressure connect to the low port For positive pressure connect to the high por...

Page 9: ...Troubleshooting www DaikinApplied com 9 IM 1093 1 SINGLE DUCT VAV TERMINALS Figure 3 MI Flow Sensor Calibration Chart ...

Page 10: ...ant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Aftermarket Services To find your local parts office visit www DaikinApplied com or call 800 37PARTS 800 377 2787 To find your local service office visit www DaikinAppli...

Reviews: