www.DaikinApplied.com 11
IM 830-6
Horizontal Room Air (Lower) Intake Duct Collar Installation
.
Figure 19: Horizontal Room Air (Lower) Intake Duct Collar Details
Horizontal room air (lower) intake
Center duct collar angle over intake opening. Use
as template and drill .125" dia. holes. Attach duct
collar angle with provided #8 sheet metal screws.
Attach angles to unit at
holes nearest to the edge.
#8 x 1-1/4" screws locate within slots on
the top duct collar angle. Holes provided.
Number of screws vary by unit size.
Horizontal Room Air (Lower) Intake and Horizontal Outdoor Air (Upper) Intake
Duct Collars Installation
Remove the lower knockout panel and the upper knockout panel using a hammer and flat screw driver or punch. Install the duct
flanges as shown in
Figure 20: Horizontal Room Air (Lower) Intake Duct Collar and Horizontal Outdoor Air (Upper) Intake Details
Attach angles to unit at
holes nearest to the edge.
Center duct collar angle over intake opening. Use
as template and drill .125" dia. holes. Attach duct
collar angle with provided #8 sheet metal screws.
Center duct collar angle over intake opening. Use
as template and drill .125" dia. holes. Attach duct
collar angle with provided #8 sheet metal screws.
Horizontal outdoor air (upper) intake
Horizontal room air (lower) intake
#8 x 1-1/4" screws locate within slots on the
top and bottom duct collar angles. Holes
provided. Number of screws vary by unit size.
When both horizontal
room air and outdoor air
duct collar angles are
used, duct collar angles
overlap as shown.