IM 830-6
46 www.DaikinApplied.com
Local User Interface (LUI)
Figure 82: Local User Interface (LUI)
The optional built-in LUI touch pad with digital OLED display
is located in the right hand compartment below the top right
access door. The 4 x 20 OLED display will provide a variety of
information including:
Operating Mode States
• Fan functions
• Room set point temperature
• Current room temperature
• Fault codes for quick diagnostics at the unit
The LUI has a built in menu structure (Password protected)
with 4 keys and 2 individual LED indicators to adjust the unit
ventilator operating parameters shown in the following.
Operating Mode States (4)
•
Heat –
Heating and economizer operation only
•
Cool –
Cooling and economizer operation only
•
Fan Only –
Fan operation only
•
Auto –
Unit automatically switches between heating,
cooling and economizer operation to satisfy the room load
conditions. The current unit state is also displayed.
Fan States (4)
•
High (constant speed)
•
Medium (constant speed)
•
Low (constant speed)
•
Auto (part load, variable air) – Varies the fan speed
automatically to meet the room load conditions whether
the unit is in heating, cooling or economizer mode. The
current fan speed is also displayed. During low load
or normal operation (about 60% of the time) the fans
will operate at low speed. When the load increases to
an intermediate demand the fans automatically shift to
medium speed. At near design or design load conditions,
the fans will operate on high speed. A 10-minute delay
between speed changes is incorporated to minimize the
awareness of these changes. The outdoor air damper will
index based on the fan speed to maintain the required
minimum cfm (cubic feet per minute) of ventilation air.
Occupancy Modes (4)
•
Occupied –
Normal, daytime operation where the unit
maintains the room set point.
•
Unoccupied –
Night set back operating mode in which
the unit responds to a new room set point and cycles to
maintain the condition. The fan comes on when heating
or cooling is needed and runs until the load is satisfied.
The outside air damper is closed during this mode. With
direct expansion (DX) cooling units, when a cooling load
is satisfied by the refrigerant system, the compressor is
de-energized and the Unit Ventilator indoor fan continues
to run for a fixed period of time to remove possible frost
buildup on the evaporator coil.
•
Stand By Mode –
The unit ventilator maintains the stand
by mode set point temperature with the outside air damper
closed. The fan runs continuously unless it is configured to
cycle in response to the room load.
•
Bypass Mode –
By depressing the Tenant Override Switch
(Item 4) the unit is placed back into the Occupied Mode for a
predetermined time (default of 120 minutes). This time can
be set in 1-minute increments from 1 minute to 240 minutes
through the Unit Ventilator Service Tool or a network.
Table 39: Wiring Diagram Legend for
Figure 83 on page 47 and Figure 84
Symbol Description
Symbol Description
Symbol Description
A1
Actuator- Outdoor Air
HP
High Pressure Switch
R32
Relay - Drain Pan Heater
A2
Actuator- Face & Bypass
ICT
Sensor - Indoor DX Coil Temperature
R28
Relay - Outdoor Motor Air
CP1
Motor Compressor 2-Stage
IH
Sensor - Indoor Humidity
RV
Reversing Valve
C1
Compressor Contactor
MCB
Main Control Board
RAT
Sensor - Room Air Temperature
CAP1
Capacitor Run
NTWK
Network Connection
T6
Thermostat - Freeze Stat
CEH1-3
Electric Heat Contactor
OAT
Sensor - Outdoor Air Temperature
TB1
Terminal Block - 24VAC+
CO2
Sensor - Indoor Air CO2
OCT
Sensor - Outdoor DX Coil Temperature
TB2
Terminal Block – 24VAC Gnd
DAT
Sensor - Discharge Air Temperature
OH
Sensor - Outdoor Humidity
TB3
(A, B) Terminal Block – Main Power
DCS
Switch - Unit Power
OH1
Thermostat - Overheat
TBE
Terminal Block - Electric Heat
DF
Dead Front Switch
OH2
Thermostat - Overheat
TR1
Transformer - Motor Speed
EH1-6
Heater - Electric
OHM
E.H. Man Reset - Overheat Stat
TR3
Transformer - 208 / 230V-24V, 75VA
EH10
Heater - Outdoor Drain Pan
PL1
LED Occupancy / Fault Status
TR4
Transformer - 460V–230V
F1A/F1B
Fuse - Compressor
R1-R3
Relay Electric Heat (Backup)
TR5
Transformer - 208 / 230V-24V
F2A/F3C
Fuse - Electric Heat
R10-R12
Relay – Electric Heat
V1
Valve - Heat EOC (Accessory)
FA/FB
Fuse– Control, Load
R4H
Relay – Fan High Speed
V2
Valve - Cool EOC (Accessory)
FC/FD
Fuse– Control, Transformer
R4M
Relay– Fan Medium Speed
VH
Valve - Heat (Accessory)
FMI
Motor - Room Fan
R4L
Relay– Fan Low Speed
VC
Valve - Cool (Accessory)
FMO
Motor Outdoor Air
Notes:
1. All electrical installation must be in accordance with national and local electrical codes and job wiring schematic.
External wiring options - see IM for the different configured options, wiring to be minimum 18 gauge, 90°C.
3. EC motors are factory programmed for specified air flow. Contact Daikin Applied for replacement.
4. Cap extra wire. Switch wire 42A to red wire for 208V operation.
5. Switch wire 509 to terminal 2 for 208V operation.
6. Devices in legend may or may not be on unit.