IM 830-6
50 www.DaikinApplied.com
MicroTech Wall Mounted Sensor
WARNING
Rigorously adhere to field wiring procedures regarding proper
lockout and tagout of components.
WARNING
To avoid electrical shock, personal injury or death:
1. Installer must be qualified, experienced technician.
2. Disconnect power supply before installation to prevent
electrical shock and damage to equipment.
3. Make all connections in accordance with electrical wiring
diagrams, and in compliance with national and local codes.
Use copper conductors only.
4. Do not exceed ratings of the device. This is a low voltage
device: Never apply more than 12VAC/VDC to any lead or
damage will result.
5. Avoid locations where excessive moisture, corrosive fumes,
or vibrations are present.
Note:
Avoid placing wall sensor near drafty areas such as doors or
windows. Avoid external walls, or dead spots near exposed columns.
Avoid direct sunlight on wall sensor.
Figure 87: Wall Mounted Temperature Sensor
When Using A Remote Temperature
Sensor
If a decision is made to use a Wall Mounted Temperature
Sensor instead of the unit mounted room air sensor then
placement of the Remote Wall Mounted Temperature Sensor
is critical for proper room temperature sensing (see
). The UVC is capable of using one of four
remote wall mounted temperature sensors. It is recommended
that additional wires be pulled to compensate for potential wire
breakage or future options.
• 6-Button
Digital Adustable Sensor (PN 910247458) 8-wires
• 4-Button
Digital Adustable Sensor (PN 910247448) 6-wires
• The
Basic Sensor with setpoint adjustment (PN
910247453) 4-wires
• The
Basic Sensor (PN 910247450) 3-wires
For sensor terminal wiring details see the installation manual specific
to the sensor being used.
NOTICE
Figure 88: Correct Wall Sensor Locations
Window Exposure
Window Exposure
Window Exposure
Interior Wall
Interior Wall
Interior Wall
Interior Wall
Unit
Unit
= Correct Sensor Location
Window Exposure
Figure 89: Incorrect Unit and Wall Sensor Locations
= Incorrect Sensor Location
Window Exposure
Interior Wall
Interior Wall
Window
Exposure
Unit
Unit
Interior Wall
Interior Wall
Window Exposure
Cubicle Wall
Shelving
File Cabinet
Shelving
Note:
Avoid placing wall sensor near drafty areas such as doors or
windows. Avoid external walls, or dead spots near exposed columns.
Avoid direct sunlight on wall sensor.
Table 40: Max Sensor Wire Length and Gauge
Maximum sensor wire length for less than 1
º
F error
Gauge
14 AWG
16 AWG
18 AWG
20 AWG
Length
800 ft. (244 m) 500 ft. (152 m)
310 ft. (94 m)
200 ft. (61 m)