IM 830-6
64 www.DaikinApplied.com
To avoid electrical shock, personal injury or death, be sure that field
wiring complies with local and national fire, safety, and electrical
codes, and voltage to the system is within the limits shown in the
job-specific drawings and unit electrical data plate(s).
Power supply to unit must be disconnected when making field
connections. Rigorously adhere to field wiring procedures regarding
proper lockout and tag out of components.
WARNING
!
Table 44: Ceiling - AH Electrical Data/Motor Data and Unit Amp Without Electric Heat
Unit
Series
CFM
ESP
Motor
Unit Current
Unit MCA
Fuse or Breaker
Nominal
L/s
iwc
Pa
HP
Watts 115V 208V 230V 265V 115V 208V 230V 265V 115V 208V 230V 265V
H07/V07
750
354
0-.45
0-112.5
1/3
246
5.0
3.0
2.8
2.6
6.3
3.8
3.5
3.3
15
15
15
15
H10/V10
1000
472
0-.45
0-112.5
1/3
246
5.0
3.0
2.8
2.6
6.3
3.8
3.5
3.3
15
15
15
15
H13/V13
1250
590
0-.45
0-112.5
1/3
246
5.0
3.0
2.8
2.6
6.3
3.8
3.5
3.3
15
15
15
15
H15/V15
1500
708
0-.45
0-112.5
1/3
246
5.0
3.0
2.8
2.6
6.3
3.8
3.5
3.3
15
15
15
15
H20/V20
2000
944
0-.45
0-112.5
3/4
560
9.6
7.3
6.8
5.5
12.0
9.1
8.5
6.9
20
15
15
15
Notes:
Unit wire sizing should be determined in accordance with NEC and local codes.
#
Amps at unit voltage, 60 Hz, single phase
Table 45: Standard Motor Electric Heat Capacities, Amps, Wire Sizing, and Over Current Protection
Unit Type
AHF
AHV
AHR
AHV
AHR
AHF
AHV
AHR
AHV
AHR
AHF
AHV
AHR
AHV
AHR
AHF
AHV
AHR
AHV
AHR
AHF
AHV
AHR
AHV
AHR
CFM
750(H07), (V07)
1000(H10), (V10)
1250(H13), (V13)
1500(H15), (V15)
2000(H20), (V20)
Number of Electric Elements
3
6
3
6
3
6
3
6
3
6
kW
6
12
8
16
10
20
12
24
12
24
MBh
20.5
41
27.3
54.6
34.1
68.3
41
81.9
41
81.9
Final Air Temp F (70°F EAT)
95.2
120.3
95.2
120.3
95.2
120.3
95.2
120.3
88.9
107.7
Air Temp Rise
25.2
50.3
25.2
50.3
25.2
50.3
25.2
50.3
18.9
37.7
208-60-1
Electric Heating Amps
28.9
57.7
38.5
76.9
48.1
96.2
57.7
115.4
57.7
115.4
Unit Minimum Circuit Ampacity
39.8
75.9
51.8
99.9
63.9
123.9
75.9
148
81.2
153.4
Max Fuse Size or Circuit Breaker
40
80
60
100
70
125
80
150
90
175
230-60-1
Electric Heating Amps
25
50
33.3
66.7
41.7
83.3
50
100
50
100
Unit Minimum Circuit Ampacity
34.8
66
45.2
86.8
55.6
107.7
66
128.5
71
133.5
Max Fuse Size or Circuit Breaker
35
70
50
90
60
110
70
150
80
150
265-60-1
Electric Heating Amps
21.7
43.3
28.9
57.8
36.1
72.2
43.3
86.6
43.3
86.6
Unit Minimum Circuit Ampacity
30.3
57.4
39.4
75.5
48.4
93.5
57.4
111.6
61
115.2
Max Fuse Size or Circuit Breaker
35
60
40
80
50
100
60
125
70
125
208-60-3
Electric Heating Amps
16.7
33.4
22.2
44.5
27.8
55.6
33.4
66.7
33.4
66.7
Unit Minimum Circuit Ampacity
24.6
45.4
31.5
59.3
38.5
73.2
45.4
87.1
50.8
92.5
Max Fuse Size or Circuit Breaker
25
50
35
60
40
80
50
90
60
100
230-60-3
Electric Heating Amps
14.5
28.9
19.3
38.5
24.1
48.2
28.9
57.8
28.9
57.8
Unit Minimum Circuit Ampacity
21.6
39.6
27.6
51.7
33.6
63.7
39.6
75.8
44.6
80.8
Max Fuse Size or Circuit Breaker
25
40
30
60
35
70
40
80
40
90
460-60-3
Electric Heating Amps
7.2
14.5
9.6
19.3
12
24.1
14.5
28.9
14.5
28.9
Unit Minimum Circuit Ampacity
10.6
19.6
13.6
25.7
16.6
31.7
19.6
37.7
21.1
39.1
Max Fuse Size or Circuit Breaker
15
25
20
30
20
35
25
40
25
40
Note:
Electric heat disconnect provided.