Part
3. Commissioning Procedure
110
Design Guide
DCM014A51
3.2 Indoor Unit Points (for each indoor unit)
Instance Number
Object Name
Type
1
Occupancy Mode
MO
2
Unit On_Off Status
BI
3
Alarm Status
BI
4
Operation Mode
MV
5
Room Temperature
AI
6
Occ Cooling Setpoint
AV
7
Occ Heating Setpoint
AV
8
Unocc Cooling Setpoint
AV
9
Unocc Heating Setpoint
AV
10
Max Cooling Setpoint
AV
11
Min Cooling Setpoint
AV
12
Max Heating Setpoint
AV
13
Min Heating Setpoint
AV
14
Min Setpoint Differential (Cooling & Heating)
AV
15
Setpoint Tracking Mode
BV
16
Fan Speed
MV
17
Airflow Direction
MV
18
Timed Override Operation
BV
19
Current Unit Operation
MI
20
RC On Off
MV
21
RC Operation Mode
BV
22
RC Setpoint
BV
23
Filter Sign Status
BI
24
Filter Sign Reset
BV
25
Indoor Fan Status
BI
26
Communication Status
BI
27
Thermo On Status
BI
28
Compressor Status
MI
29
Aux Heater Status
BI
30
Forced Thermo-off
BV
31
Indoor Unit Changeover Option
BI
32
Return Air Temperature
AI
33
Discharge Air Temperature
AI
34
Liquid Pipe Temperature
AI
35
Gas Pipe Temperature
AI
36
EV Position
AI
37
Freeze Protection
BI
Note: Shaded points are not available by default and will need to be enabled during the
iTM
BACnet® Server Gateway commissioning.