Part
3. Commissioning Procedure
120
Design Guide
DCM014A51
5. Connecting the test operation PC and
iTM
via the cross cable or
the hub/switch using 100BASE-TX straight cable.
5.1 Connecting a Test PC to the
iTM
.
Verify that the CSV file is commissioned correctly and the required points are visible to the BMS by
using a BACnet® discovery tool/software (ex. Yabe or Cimetrics).
1. Configure network setting of your laptop to communicate to
iTM
on the same subnet.
•
iTM
Network Settings example:
IP:192.168.0.1
(default)
Subnet Mask: 255.255.255.0
(default)
• PC Network Settings example:
IP:192.168.0.2
Subnet Mask: 255.255.255.0
2. Connect laptop to
iTM
using one of the following methods:
• Ethernet crossover cable.
• Straight Ethernet cables and a network hub/switch.
5.2 Configuring
iTM
Network Settings
1. From the [Menu List] of the
iTM
select the [System Settings].
2. Select the [Network] button.
a. Modify the
iTM
IP address, Subnet Mask, and Default Gateway.
5.3 Configuring PC Network Settings
1. From the PC
Control Panel
, double-click on
Network and Sharing Center
.
2. Click on
Local Area Connection
or on the top left corner
Change Adopter Settings
, then
double-click on
Local Area Connection
.