Part
2. Functional Specifications
26
Design Guide
DCM014A51
Instance
No.
Object_Name
Type
Inactive
Active
Remarks
Text-1
Text-2
Text-3
Text-4 Text-5 Text-6 Text-7 Text-8
20
Remote Controller
Prohibit
(On_Off)
MV
Permit
Prohibit Stop Only
21
Remote Controller
Prohibit
(Operation Mode)
BV
Permit
Prohibit
22
Remote Controller
Prohibit
(Setpoint)
BV
Permit
Prohibit
23
Filter Sign Status
BI
Normal
Alarm
24
Filter Sign Reset
BV
Reset
Alarm
25
Indoor Fan Status
BI
Off
On
26
Communication
Status
BI
Normal
Alarm
27
Thermo-on Status
BI
Off
On
28
Compressor Status
MI
Off
On
Defrost/
Hot Start
29
Aux Heater Status
BI
Off
On
30
Forced Thermo-off
BV
Disable
Enable
31
Indoor Unit
Changeover Option
BI
Not
Available
Available
32
Return Air
Temperature
AI
*1, *2
33
Discharge Air
Temperature
AI
*1, *2
34
Liquid Pipe
Temperature
AI
*1, *2
35
Gas Pipe
Temperature
AI
*1, *2
36
EV Position
AI
*2
37
Freeze Protection
BI
Off
On
*3
*1: The unit of temperature (Celsius or Fahrenheit) follows the iTM locale (regional settings).
*2: The number of valid digits for each object is shown in the table below.
If a value entered from BMS has a higher precision than the number of significant digits of an
object, the digits after the significant digits are rounded.
(For example, when Occ Cooling Setpoint is "75.55" in degrees Fahrenheit, round it to "76".)
Regarding values in commands sent from the BMS, the iTM rounds them off to the number of the
significant digits.
(For example, if the value in a command for Occ Cooling Setpoint is "75.55" in degrees Fahrenheit,
it is rounded to "76".)