Part
2. Functional Specifications
66
Design Guide
DCM014A51
Notes:
1. When more than one indoor unit is connected to a single remote controller group, the
BMS should only send commands to the indoor unit that is designated to receive the
command for the remote controller group (unit #0). BMS should not send commands to
other indoor units in the remote control group. If this object is sent to the other indoor
units in the remote controller group, the indoor unit will not execute the command.
2. Relinquish_Default property is fixed to "INACTIVE".
22. Remote Controller Prohibit (Setpoint)
Member number: 22
Object name:
Remote Controller Prohibit (Setpoint)
Object type:
Binary Value
Description:
Permits/Prohibits change of setpoints from the remote
controller connected to the indoor unit.
Present_Value property:
ACTIVE:
Prohibit
INACTIVE:
Permit
Notes:
1. When more than one indoor unit is connected to a single remote controller group, the
BMS should only send commands to the indoor unit that is designated to receive the
command for the remote controller group (unit #0). BMS should not send commands to
other indoor units in the remote control group. If this object is sent to the other indoor
units in the remote controller group, the indoor unit will not execute the command.
2. Relinquish_Default property is fixed to "INACTIVE".
23. Filter Sign Status
Member number: 23
Object name:
Filter Sign Status
Object type:
Binary Input
Description:
Monitors the filter sign status for the indoor unit filter.
Present_Value property:
ACTIVE:
Alarm
INACTIVE:
Normal
24. Filter Sign Reset
Member number: 24
Object name:
Filter Sign Reset
Object type:
Binary Value
Description:
Resets the filter sign status for the indoor unit filter.
Present_Value property:
ACTIVE:
Alarm
INACTIVE:
Reset
Notes:
1. Present_Value readout
This object becomes ACTIVE when "Filter Sign Status" becomes ACTIVE.