Unit Controller
www.DaikinApplied.com 47
IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR
NOTE:
Any signal less than 4 mA does not limit the chiller
capacity
Network Limit
The maximum unit capacity can be limited by a network signal.
This function is only enabled if the unit control source is set to
network. The maximum unit capacity stage is based on the
network limit value received from the BAS, and is determined
as shown in the following graph.
NOTE:
In order to allow all stages to run, a signal of 100.0%
is required.
Maximum LWT Rate
The maximum rate at which the leaving water temperature
can drop is limited by the Maximum Pull Down Rate set point
when the unit mode is cool. If the rate exceeds this set point,
no more compressors shall be started until the pull down rate
is less than the set point. Running compressors will not be
stopped as a result of exceeding the maximum pull down rate.
Summary of Contents for IOM 1322-1
Page 4: ......
Page 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Page 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Page 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...