Installation Manual
EDUS041016
32
Room Air Conditioners J-Series
8
Indoor Unit Installation
4.
Wiring
1) As shown in the illustration, insert the wires including the ground wire into the conduit and secure them with lock nut onto
the conduit mounting plate.
2) Strip wire ends (9/16 inch (15mm)).
3) Match wire colors with terminal numbers on indoor and outdoor unit’s terminal blocks and firmly screw wires to the
corresponding terminals.
4) Connect the ground wires to the corresponding terminals.
5) Pull wires to make sure that they are securely latched up.
6) In case of connecting to an adapter system. Run the remote control cable and attach the S21.
7) Shape the wires so that the service lid fits securely, then close service lid.
WARNING
• Do not use tapped wires, strand wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• When carrying out wiring connection, take care not to pull at the conduit.
5.
When connecting to a wired remote controller
* If work space is available on the right side of the indoor unit, the work
can be performed with the electrical component box attached. Omit the
steps involved with removing and installing the electrical component
box in order to perform the work more efficiently.
5-1. Remove the front grille (2 screws).
5-2. Remove the service lid (1 screw).
5-3. Remove the cover from the indoor unit electrical
component box [Figure 1].
* 5-4.Remove the indoor unit electrical component box.
1) Remove the louver.
2) Disconnect the communication wiring.
3) Disconnect the connector (S200).
4) Remove the thermistor from the heat exchanger.
5) Remove the electrical component box installation screw (1 screw).
1
2
3
Terminal block
Electrical component box
Use the specified wire type.
Shape wires so that the
service lid will fit securely.
1
2
3
1 2 3
L
1
L
2
When wire length exceeds
33ft (10m), use AWG14 wires.
Outdoor unit
Indoor
unit
Conduit
mounting
plate
Conduit
Lock nut
Back
Use AWG16 or AWG14 wire
for the inter-unit wiring.
Disengage the tab.
Figure 1: Removing the cover from
the indoor unit electrical
component box
Disengage the tab.
Cover of the indoor unit
electrical component box
Summary of Contents for J Series
Page 1: ...EDUS041016 J Series Cooling Only Heat Pump SEER 13 Models ...
Page 53: ...Operation Manual EDUS041016 52 Room Air Conditioners J Series 12 2 Operation Instructions ...
Page 54: ...EDUS041016 Operation Manual Room Air Conditioners J Series 53 ...
Page 55: ...Operation Manual EDUS041016 54 Room Air Conditioners J Series ...
Page 56: ...EDUS041016 Operation Manual Room Air Conditioners J Series 55 ...
Page 57: ...Operation Manual EDUS041016 56 Room Air Conditioners J Series ...
Page 58: ...EDUS041016 Operation Manual Room Air Conditioners J Series 57 ...
Page 59: ...Operation Manual EDUS041016 58 Room Air Conditioners J Series ...
Page 60: ...EDUS041016 Operation Manual Room Air Conditioners J Series 59 ...
Page 61: ...Operation Manual EDUS041016 60 Room Air Conditioners J Series ...
Page 62: ...EDUS041016 Operation Manual Room Air Conditioners J Series 61 ...
Page 63: ...Operation Manual EDUS041016 62 Room Air Conditioners J Series ...
Page 64: ...EDUS041016 Operation Manual Room Air Conditioners J Series 63 ...
Page 65: ...Operation Manual EDUS041016 64 Room Air Conditioners J Series ...
Page 66: ...EDUS041016 Operation Manual Room Air Conditioners J Series 65 ...
Page 67: ...Operation Manual EDUS041016 66 Room Air Conditioners J Series ...
Page 68: ...EDUS041016 Operation Manual Room Air Conditioners J Series 67 ...
Page 69: ...Operation Manual EDUS041016 68 Room Air Conditioners J Series ...
Page 70: ...EDUS041016 Operation Manual Room Air Conditioners J Series 69 ...
Page 71: ...Operation Manual EDUS041016 70 Room Air Conditioners J Series ...
Page 72: ...EDUS041016 Operation Manual Room Air Conditioners J Series 71 ...
Page 73: ...Operation Manual EDUS041016 72 Room Air Conditioners J Series ...
Page 74: ...EDUS041016 Operation Manual Room Air Conditioners J Series 73 ...
Page 75: ...Operation Manual EDUS041016 74 Room Air Conditioners J Series ...
Page 76: ...EDUS041016 Operation Manual Room Air Conditioners J Series 75 ...
Page 77: ...Operation Manual EDUS041016 76 Room Air Conditioners J Series 3P253185 2 ...