background image

EDUS041016

Operation Manual

Room Air Conditioners J-Series

59

Summary of Contents for J Series

Page 1: ...EDUS041016 J Series Cooling Only Heat Pump SEER 13 Models ...

Page 2: ...7 2 Heat Pump 14 7 3 Capacity correction factor by the length of refrigerant piping Reference 18 8 Operation Limit 19 9 Sound Level 20 9 1 Measuring Location 20 9 2 Octave Band Level 21 10 Electric Characteristics 23 11 Installation Manual 24 11 1 Indoor Units Safety Considerions 24 11 2 Indoor Unit Installation Instructions 26 11 3 Outdoor Units Safety Considerions 37 11 4 Outdoor Units Installat...

Page 3: ...fety Considerations 49 12 2 Operation Instructions 52 13 Optional Accessories 77 13 1 Option List 77 13 2 BRC944B2 Wired Remote Controller 78 13 3 KRP980B1 Interface Adaptor for Wired Remote Controller 92 13 4 KPW937A4 Air Direction Adjustment Grille 96 ...

Page 4: ... J Series 3 1 Power Supply Note Power Supply Intake Outdoor Unit Indoor Units Outdoor Units Power Supply The Single Split Duct Free System FTKN09JEVJU RKN09JEVJU 1 208 230V 60Hz FTKN12JEVJU RKN12JEVJU FTXN09JEVJU RXN09JEVJU FTXN12JEVJU RXN12JEVJU ...

Page 5: ... Failure Vertical Auto Swing Up and Down Self Diagnosis Digital LED Display Horizontal Auto Swing Right and Left Wiring Error Check 3 D Airflow Anti Corrosion Treatment of Outdoor Heat Exchanger COMFORT AIRFLOW Operation Flexibility Multi Split Split Type Compatible Indoor Unit Comfort Control Auto Fan Speed Flexible Voltage Correspondence Indoor Unit Quiet Operation High Ceiling Application NIGHT...

Page 6: ...ft Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 20 0 18 0 20 0 18 Power Consumption Rated W 40 40 Power Factor 96 2 96 6 96 2 96 6 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D inch 11 9 64 30 5 16 7 51 64 11 9 64 30 5 16 7 51 64 Packaged Dimensions H W D inch 10 17 64 33 7 32 13 15 32 10...

Page 7: ...teps Quiet Auto Air Direction Control Right Left Horizontal Downward Right Left Horizontal Downward Air Filter Removable Washable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 20 0 18 0 20 0 18 Power Consumption Rated W 40 40 Power Factor 96 2 96 6 96 2 96 6 Temperature Control Microcomputer Control Microcomputer Control Dimensions H W D inch 11 9 64 30 5 16 7 51 64 11 9 6...

Page 8: ...RIGHT LEFT MANUAL φ2 9 16 φ65mm HOLE WALL HOLE φ2 9 16 φ65mm HOLE STANDARD LOCATIONS OF WALL HOLES WIRELESS REMOTE CONTROLLER 45 45 ARC452A14 3D065952B AIRFLOW INDOOR THE MARK SHOWS PIPING DIRECTION REAR 30 5 16 770mm RIGHT LEFT 1 3 16 30mm MIN INCLUDING MOUNTING PLATE SPACE FOR PERFORMANCE 7 7 8 200mm 1 15 16 50mm MIN 1 15 16 50mm MIN 7 51 64 198mm SPACE FOR SPACE FOR FRONT PANEL FIXING SCREWS RE...

Page 9: ...OOR AIR THERMISTOR BRAND NAME LABEL MANUFACTURE S LABEL HANDLE 5 16 8 5 16 8 1 31 32 50 10 13 16 275 15 32 12 25 29 32 658 LIQUID STOP VALVE 1 4 φ6 4 CuT SERVICE PORT 21 21 32 550 6 5 8 168 6 3 32 155 WALL HEIGHT ON AIR OUTLET SIDE MINIMUM SPACE FOR AIR PASSAGE 4 1 4 108 LESS THAN 47 3 16 1200 IN CASE OF REMOVING GAS STOP VALVE STOP VALVE 3 8 φ9 5 CuT 5 7 8 150 5 7 8 150 1 15 16 50 1 15 16 50 1 15...

Page 10: ...t RESTART AUTOMATICALLY IF X1M 3 15A THE MAIN POWER SUPPLY IS R1T TURNED OFF AND THEN BACK IPM200 SIGNAL ON AGAIN RECEIVER 1 1 1 2 5 10 S403 12 9 1 6 S32 S200 S6 INDOOR BLK BLK BLK BLK BLK BLK BLK BLK BLK BLK BLK BLK YLW BLK BLK BLK WIRELESS BLU BLK RED WHT ORG FG REMOTE F1U 1 4 1 6 S601 S602 CONTROLLER H1 H3 M M H1P H2P t M1S M1F M1F R2T M1S PCB1 PCB3 R1T R2T NOTE S6 S602 S21 S1W 1 PCB3 SHOWS THE...

Page 11: ...CuT 9 32CuT THERMISTOR ON HEAT EXCH 9 32CuT 9 32CuT CROSS FLOW FAN FIELD PIPING 1 4CuT M FAN MOTOR 3 8CuT FIELD PIPING 3 8CuT REFRIGERANT FLOW COOLING 4D066315 INDOOR UNIT HEAT EXCHANGER 9 32CuT 3 16CuT 9 32CuT THERMISTOR ON HEAT EXCH 9 32CuT 9 32CuT CROSS FLOW FAN FIELD PIPING 1 4CuT M FAN MOTOR 3 8CuT FIELD PIPING 3 8CuT REFRIGERANT FLOW COOLING HEATING 4D066211 ...

Page 12: ...IELD PIPING 3 8CuT DISCHARGE PIPE COOLING COMPRESSOR THERMISTOR 3 8CuT GAS STOP VALVE ACCUMULATOR 3D066384 OUTDOOR UNIT OUTDOOR TEMPERATURE HEAT EXCHANGER 9 32CuT THERMISTOR 9 32CuT 3 8CuT CAPILLARY CHECK VALVE TUBE 1 3 16CuT 1 4CuT 1 4CuT 3 16CuT MUFFLER THERMISTOR WITH HEAT EXCHANGER FAN CAPILLARY FILTER MOTOR TUBE 2 M PROPELLER FAN 1 4CuT 3 8CuT 3 8CuT FOUR WAY VALVE ON HEATING FIELD PIPING 3 1...

Page 13: ...0 73 7 76 5 30 0 75 7 52 5 11 0 79 7 13 4 80 0 79 60 8 71 6 9 10 6 05 0 61 8 70 5 71 0 67 8 31 5 39 0 73 8 15 5 27 0 75 7 91 5 08 0 79 7 52 4 79 0 80 64 4 77 0 9 49 6 09 0 62 9 10 5 78 0 68 8 70 5 47 0 73 8 54 5 35 0 76 8 30 5 17 0 79 7 91 4 89 0 80 67 0 80 0 9 69 6 18 0 62 9 29 5 86 0 68 8 90 5 56 0 74 8 74 5 45 0 76 8 50 5 27 0 80 8 10 5 00 0 80 71 6 86 0 10 27 5 93 0 62 9 88 5 64 0 68 9 48 5 36...

Page 14: ...3 0 89 7 78 5 33 0 92 60 8 71 6 10 41 7 29 0 72 10 24 7 13 0 80 9 77 6 69 0 87 9 59 6 51 0 90 9 31 6 26 0 94 8 84 5 86 0 95 64 4 77 0 11 17 7 64 0 73 10 70 7 20 0 80 10 24 6 77 0 87 10 05 6 60 0 90 9 77 6 36 0 94 9 30 5 97 0 95 67 0 80 0 11 40 7 72 0 74 10 93 7 28 0 81 10 47 6 86 0 88 10 28 6 70 0 90 10 00 6 46 0 95 9 53 6 08 0 95 71 6 86 0 12 09 7 45 0 74 11 62 7 04 0 81 11 16 6 65 0 88 10 97 6 5...

Page 15: ...9 0 80 64 4 77 0 9 49 6 09 0 62 9 10 5 78 0 68 8 70 5 47 0 73 8 54 5 35 0 76 8 30 5 17 0 79 7 91 4 89 0 80 67 0 80 0 9 69 6 18 0 62 9 29 5 86 0 68 8 90 5 56 0 74 8 74 5 45 0 76 8 50 5 27 0 80 8 10 5 00 0 80 71 6 86 0 10 27 5 93 0 62 9 88 5 64 0 68 9 48 5 36 0 74 9 32 5 26 0 77 9 09 5 10 0 80 8 69 4 84 0 81 75 2 89 6 10 67 5 72 0 63 10 27 5 45 0 69 9 87 5 19 0 75 9 72 5 09 0 77 9 48 4 94 0 80 9 08 ...

Page 16: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level difference 0 ft 6 Airflow rate AFR and Bypass factor BF are tabulated above table BF Bypass factor EWB Entering wet bu...

Page 17: ... 17 7 64 0 73 10 70 7 20 0 80 10 24 6 77 0 87 10 05 6 60 0 90 9 77 6 36 0 94 9 30 5 97 0 95 67 0 80 0 11 40 7 72 0 74 10 93 7 28 0 81 10 47 6 86 0 88 10 28 6 70 0 90 10 00 6 46 0 95 9 53 6 08 0 95 71 6 86 0 12 09 7 45 0 74 11 62 7 04 0 81 11 16 6 65 0 88 10 97 6 50 0 91 10 69 6 28 0 95 10 23 5 92 0 96 75 2 89 6 12 55 7 20 0 75 12 08 6 82 0 82 11 62 6 45 0 89 11 43 6 31 0 91 11 15 6 10 0 96 10 69 5...

Page 18: ...tables Figures out of the tables should not be used for calculation 4 About SHC which are not mentioned on the table please calculate them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25 ft Level difference 0 ft 6 Airflow rate AFR and Bypass factor BF are tabulated above table BF Bypass factor EWB Entering wet bu...

Page 19: ...e corrected in accordance with the length of refrigerant piping The distance between the indoor unit and the outdoor unit Note The graph shows the factor when additional refrigerant of the proper quantity is charged line cooling capacity line heating capacity Capacity correction factor 1 16 4 32 8 49 2 0 9 0 8 R 410A 09 12 class Piping length ft R11493 Range of the refrigerant additional charge ...

Page 20: ...following conditions Equivalent piping length 25ft Level difference 0ft Air flow rate High 4D066173A Heating Cooling 68 122 114 8 59 104 50 86 41 32 68 Pull down period Outdoor temp FWB 23 Continuous operation Outdoor temp FDB 50 Continuous operation 14 32 5 82 4 68 86 73 4 57 2 50 5 FDB Indoor temp FWB 50 86 68 Notes Indoor temp FDB The graphs are based on the following conditions Equivalent pipi...

Page 21: ...nd is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit The Single Split Duct Free System Outdoor Unit 3 3 ft 2 6 ft R5162 3 3 ft R4796 Cooling Heating Piping Length Indoor 80 FDB 67 FWB Outdoor 95 FDB 75 FWB Indoor 70 FDB 60 FWB Outdoor 47 FDB 43 FWB 25 ft ...

Page 22: ...RECTIFIED 60 50 10 20 40 30 63 OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 μ bar THRESHOLDHEARING APPROXIMATE FORCONTINUOUS NOISE POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED COOLING HEATING NC 10 NC 20 NC 30 NC 40 NC 50 NC 10 NC 20 NC 30 NC 40 NC 50 26 40 L 208 230V 60Hz H 208 230V ...

Page 23: ...CY Hz 250 500 1000 2000 4000 8000 OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED 70 60 20 30 50 40 63 OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 μ bar THRESHOLDHEARING APPROXIMATE FORCONTINUOUS NOISE POWER SOURCE JIS STANDARD OPERATING CONDITIONS OVER ALL dB SCALE A B G N IS ALREADY RECTIFIED COOLING HEATING 230V 60Hz 49 230V H 60...

Page 24: ...0 0 20 60 230 6 1 0 26 0 18 FTXN12JEVJU RXN12JEVJU 60 208 MAX 60Hz 253V MIN 60Hz 187V 8 3 15 6 7 59 0 29 40 0 20 60 230 6 1 0 26 0 18 Symbols Note MCA MIN CIRCUIT AMPS A 1 Maximum allowable voltage variation between phases is 2 2 Select wire size based on the larger value of MCA 3 Instead of fuse use circuit breaker 4 Be sure to install an ground leak detector One that can handle higher harmonics ...

Page 25: ...king materials such as nails and other metal or wood parts including plastic packing materials used for transportation may cause injuries or death by suffocation Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a sma...

Page 26: ...odels that can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed e...

Page 27: ...ay from electronic ignition type fluorescent lamps inverter or rapid start type as they may shorten the remote controller range 8 the unit is at least 3 5 feet 1m away from any television or radio set unit may cause interference with the picture or sound 9 no laundry equipment is located 2 Wireless remote controller 1 Turn on all the fluorescent lamps in the room if any and find the site where rem...

Page 28: ...n there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the center of the front grille and while pushing up pull it toward you Installation method 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 2 screws of the front grille 3 Install the air filter and then mount the front panel 3 How to set t...

Page 29: ...the mounting plate If the claws are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille The mounting plate should be installed on a wall which can support the weight of the indoor unit 1 3 16 30mm or more from ceiling Front panel 1 15 16 50mm ...

Page 30: ...ing plate retention spots and dimensions The removed pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate Use tape measure as shown Position the end of a tape measure at Liquid pipe end Gas pipe end Through the wall hole φ2 9 16 φ65 Recommended mounting plate retention spots 5 spots in all Place a leveler on raised tab 9 33 64 241 7 1 5 8 41 3 13 1 64 3...

Page 31: ...inyl tape 2 Wrap the refrigerant pipes and drain hose together with insulation tape 3 Pass the drain hose and refrigerant pipes through the wall hole then set the indoor unit on the mounting plate hooks by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid 5 Pass the inter unit wiring from the outdoor unit through the feed through wall hole...

Page 32: ...crews on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing screw Forgetting to tighten this may cause water leakages How to replace the drain plug and drain hose Drain hose attachment position The drain hose is on the back of the unit Front side of unit Attachment on the r...

Page 33: ...ing out wiring connection take care not to pull at the conduit 5 When connecting to a wired remote controller If work space is available on the right side of the indoor unit the work can be performed with the electrical component box attached Omit the steps involved with removing and installing the electrical component box in order to perform the work more efficiently 5 1 Remove the front grille 2...

Page 34: ...rate product into the indoor unit electrical component box 2 Route the connection cord as shown in Figure 3 5 8 Install the indoor unit electrical component box in its original position 1 Install the louver 2 Install the electrical component box 1 screw 3 Install the thermistor in its original position on the heat exchanger 4 Install the connector S200 in its original position 5 Connect the commun...

Page 35: ...not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a drier to this R410A unit in order to guarantee its lifetime The drying material may dissolve and damage the system Incomplete flaring may ca...

Page 36: ...mh C 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 3 8 inch 9 5mm O D 1 4 inch 6 4mm I D 0 427 0 590 inch 12 15mm I D 0 315 0 393 inch 8 10mm Minimum bend radius Thickness 0 393 inch 10m...

Page 37: ...ons and parts such as fin movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the...

Page 38: ... injuries or death by suffocation Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant leaks i...

Page 39: ... kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the air conditioner in the following locations a...

Page 40: ...nterference to images and sounds Noises may be heard even if they are more than 10 feet 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed...

Page 41: ...49 2ft 15m Max allowable height Additional refrigerant required for refrigerant pipe exceeding 33ft 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length is 4 92ft 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit ...

Page 42: ...rface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work Heat pump models 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of a...

Page 43: ...ches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A Check Flare s inner surface must be flaw free The pipe end must be evenly flared in a perfect circle Make sure that the flare nut is fitted Cut exactly at right angles Remove burrs...

Page 44: ...t projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 29 9inHg 0 1MPa 1 4 Close gauge manifold s low pressure valve Lo and sto...

Page 45: ... following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to 0 045kcal mh C Be sure to use insulation that is designed for use with HVAC Systems 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid si...

Page 46: ...p automatically after around 15 minutes To force a trial operation to stop press the indoor unit ON OFF button Using the main unit s remote controller 1 Press the ON OFF button Operation will start 2 Press the TEMP button and the MODE button at the same time 3 Press the MODE button twice will be displayed and the unit will enter trial operation 4 Press the MODE button to return the operation mode ...

Page 47: ...inal board Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection plate by removing the 2 screws and dismount the conduit mounting plate cover by removing the 1 screw Method of mounting conduit 1 Pass wires through the conduit and secure them with a lock nut 2 After completing the work reattach the conduit moun...

Page 48: ... using a single core wire be sure to perform curling Problems with the work may cause heat and fires 3 Pull the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop Strip wire end to this point Excessive strip length may cause electrical shock or leakage Good Wrong Stripping wire at terminal block ...

Page 49: ...es after it is turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as fin movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the cir...

Page 50: ...or death Be sure to ventilate the room sufficiently to avoid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them Children playing with plastic bags face the danger of death by suffocation Contact your dealer for ...

Page 51: ...cause injury Do not place objects in direct proximity of the outside unit Do not let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which can enter the unit Once inside the unit animals can cause the unit to malfunction and cause smoke or fire when they make contact with electrical parts Never press the button of the remote controller with a hard pointed o...

Page 52: ... neighbors Make sure that there are no obstacles close to the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dealer if the air conditioner in operation generates unusual noise Make sure that the drainpipe is installed properly to drain water If no water is discharged from the drainpipe w...

Page 53: ...Operation Manual EDUS041016 52 Room Air Conditioners J Series 12 2 Operation Instructions ...

Page 54: ...EDUS041016 Operation Manual Room Air Conditioners J Series 53 ...

Page 55: ...Operation Manual EDUS041016 54 Room Air Conditioners J Series ...

Page 56: ...EDUS041016 Operation Manual Room Air Conditioners J Series 55 ...

Page 57: ...Operation Manual EDUS041016 56 Room Air Conditioners J Series ...

Page 58: ...EDUS041016 Operation Manual Room Air Conditioners J Series 57 ...

Page 59: ...Operation Manual EDUS041016 58 Room Air Conditioners J Series ...

Page 60: ...EDUS041016 Operation Manual Room Air Conditioners J Series 59 ...

Page 61: ...Operation Manual EDUS041016 60 Room Air Conditioners J Series ...

Page 62: ...EDUS041016 Operation Manual Room Air Conditioners J Series 61 ...

Page 63: ...Operation Manual EDUS041016 62 Room Air Conditioners J Series ...

Page 64: ...EDUS041016 Operation Manual Room Air Conditioners J Series 63 ...

Page 65: ...Operation Manual EDUS041016 64 Room Air Conditioners J Series ...

Page 66: ...EDUS041016 Operation Manual Room Air Conditioners J Series 65 ...

Page 67: ...Operation Manual EDUS041016 66 Room Air Conditioners J Series ...

Page 68: ...EDUS041016 Operation Manual Room Air Conditioners J Series 67 ...

Page 69: ...Operation Manual EDUS041016 68 Room Air Conditioners J Series ...

Page 70: ...EDUS041016 Operation Manual Room Air Conditioners J Series 69 ...

Page 71: ...Operation Manual EDUS041016 70 Room Air Conditioners J Series ...

Page 72: ...EDUS041016 Operation Manual Room Air Conditioners J Series 71 ...

Page 73: ...Operation Manual EDUS041016 72 Room Air Conditioners J Series ...

Page 74: ...EDUS041016 Operation Manual Room Air Conditioners J Series 73 ...

Page 75: ...Operation Manual EDUS041016 74 Room Air Conditioners J Series ...

Page 76: ...EDUS041016 Operation Manual Room Air Conditioners J Series 75 ...

Page 77: ...Operation Manual EDUS041016 76 Room Air Conditioners J Series 3P253185 2 ...

Page 78: ...ame FTK X N09 12JEVJU 1 Wired Remote Controller 1 BRC944B2 2 Interface Adaptor for Wired Remote Controller KRP980B1 3 Wired Remote Controller Cord Length 3 m Shielded Wire BRCW901A03 Length 8 m Shielded Wire BRCW901A08 4 Titanium Apatite Photocatalytic Air Purifying Filter without Frame 2 KAF970A46 5 Remote Controller Loss Prevention with Chain KKF910A4 Option Name RKN09 12JEVJU RXN09 12JEVJU 1 Dr...

Page 79: ...ard or the adapter board 5 Keep the wiring away from any other power source lines to avoid electric noise external noise 6 Select a flat surface wherever possible to mount the remote controller To prevent deformation of the cases do not overtighten the mounting screws Insert a bladed screwdriver into the concave in the remote controller lower case to remove the upper case assembly two locations 1 ...

Page 80: ...tape Double face adhesive tape Attached five wire cord Remote controller cord Note 1 Connector Connector Connector Tie band to secure the cord Tie band to secure the cord Tie band to secure the cord Upper case assembly Lower case Cord drawn out on the back Catch the lower hook first Cord drawn out on the top To remote control adapter Remote controller board Remote controller board Note 1 Ground th...

Page 81: ... Adjusts the temperature setting Airflow rate button Adjusts the airflow rate Time setting button for the timer Display Timer select button Displays the operating conditions Clock setting button page 9 page 7 page 5 Selects an operation mode Displays the operating conditions Selects one of the following ONE TIME timer ON DAILY timer ON TIMER OFF CAUTION This remote controller cannot be used togeth...

Page 82: ...energy Clean the air filter monthly every two weeks as required or so Please take note of the following points Electric power is consumed even when the air conditioner is not in operation When the unit is not used for a long period of time such as during off season turn off the breaker Operating conditions If the operation is continued under any conditions other than the following the safety devic...

Page 83: ...ication is changed to Celsius one the temperature value 0 5 C will be rounded up Thus the preset temperature may be changed Example A preset temperature of 65 F equivalent to 18 5 C will be changed to 19 C 66 F by changing the temperature indication In this case if you change the Celsius temperature indication again to the Fahrenheit one the preset temperature is shown not as 65 F but as 66 F equi...

Page 84: ...en Automatic DRY Heating Cooling DRY Cooling Cooling only model Heat pump model To stop the operation Press again The run indicator lamp goes out In Automatic the temperature setting and operation mode DRY Cooling or Heating are automatically selected according to the room temperature and outdoor temperature at the time of starting operation DRY operation In this mode humidity is removed from the ...

Page 85: ...ring heating operation the heating capacity is decreased In this case the unit starts defrosting operation No hot air comes out of the indoor unit during defrosting operation To adjust the temperature and airflow rate To adjust the airflow direction page 9 Operation mode Setting to be adjusted Automatic DRY Cooling Heating Temperature Airflow rate Temperature cannot be adjusted Airflow rate cannot...

Page 86: ...troller Do not forcibly adjust louvers by hand or a malfunction may occur Adjusting Airflow Direction 1 Press during operation Each time the button is pressed the airflow direction louvers change their movement Adjust the airflow direction for maximum comfort To adjust the Airflow Direction 1 Wall Mounted Types without horizontal swing function The horizontal airflow direction louvers move up and ...

Page 87: ...ght and left The vertical airflow direction louvers stop just when the button is pressed Swing horizontally Swing vertically Airflow direction louvers stop The vertical and horizontal louvers cannot move at the same time Note The operating procedure and remote controller display are different depending on the indoor unit being connected Read How to Adjust the Airflow Direction in the air condition...

Page 88: ...inute has passed before making any timer setting the previous timer settings are reintroduced and the timer is on standby In this case use the time setting button and make your desired timer settings ONE TIME timer DAILY timer TIMER OFF ON time OFF time Timer settings displayed 1 2 4 6 3 5 The timer lamp lights up The ONE TIME or DAILY TIMER disappears from the display and the timer lamp goes out ...

Page 89: ... or decrement Hold the button down to advance quickly When the ON timer is not used save the setting as 4 Press 5 Press to make the OFF timer setting 6 Press The ONE TIME timer is now programmed Both of the ON and OFF time cannot be set as blinks When the OFF timer is not used save the setting as ONE TIME timer programmed The set time is displayed ON timer activated and system starts The ON timer ...

Page 90: ...ammed ONE TIME timer DAILY timer TIMER OFF The timer lamp lights up 1 2 1 2 ON time 24 hour timer display OFF time Timers The settings of timers and can be seen at a glance Two pairs of ON and OFF time settings can be programmed Timer settings displayed 1 2 3 2 The ONE TIME or DAILY TIMER and the timer lamp are no longer displayed Timers and programmed Timer alone programmed 1 1 2 Note The system ...

Page 91: ...ears lights up 3 Press The DAILY timer is now programmed Note If the following appears on the display the timer must be reprogrammed The 24 hour timer display is blinking The 24 hour timer display is blinking This means that Timers and are programmed for the same time settings New time settings must be made This means that the timer has not been programmed yet When the timer is not used save the s...

Page 92: ...h When the unit is not used for a long time On a sunny day keep the system running for half a day in the FAN mode to dry it up inside 3 1 2 FAN mode 1 Press to select the cooling mode 2 Press to adjust the set temperature to 32 C 90 F 3 Press The airflow rate remains the same and is not adjustable Run the system when the room temperature is below 28 C 82 F Finally turn off the circuit breaker dedi...

Page 93: ...ure Group control i e the control a number of indoor units through a single remote controller Monitoring of the following items Indoor temperature and operating conditions of thermo compressor indoor fan electric heater and humidifier Control of the following items Forced thermo OFF filter sign display and reset and air conditioner charge management Energy saving reference low noise reference and ...

Page 94: ...abs Place both hands under the center of the front grille and while pushing up pull it toward you Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand 3 locations When there is no work space because the unit is close to ceiling Removal method 1 Remove front panel to remove the air filter 2 Remove the screws 2 from the front grille 3 ...

Page 95: ...rille 3 Remove the service lid of the indoor unit 4 Remove the cover of the electrical component cover 1 Remove the flap in control of wind directions upward and downward 2 Disconnect the communication wiring see Fig 1 3 Disconnect the S200 connector see Fig 2 4 Disconnect the heat changer from the thermistor see Fig 3 5 Remove the mounting screw of the electrical component box and remove the elec...

Page 96: ...ough the cut out of the set and mount the electrical component cover to the original position 4 Insert the connector of the set into the S403 in the indoor unit electrical component connector Then route the connection cord to the cut out cut out A in the indoor unit electrical component 2 Mount the electrical component cover to the original position See Fig 2 3 Mount the set See Fig 2 1 Mount the ...

Page 97: ...rews are attached to the louver First temporarily attach the louver with 4 screws then check that the angle is correct and finally tighten the screws fully 1 Install so that a short circuit is prevented 2 For the use in snowy regions avoid installation with the air outlet facing upward Install so that the air outlet faces leftward rightward or down ward Snow accumulates in the air outlet of the ou...

Page 98: ... www daikinac com AMERICAS EDUS041016 ENGINEERING DATA SPLIT J Series Cooling Only Heat Pump Specifications designs and other content appearing in this brochure are current as of April 2010 but subject to change without notice EDUS041016 Printed in U S A 04 2010 B AK ...

Reviews: