Removal of Indoor Heat Exchanger
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure
Points
1. Disconnect the refrigerant
piping.
Preparation
Remove the electrical box
according to the “Removal
of Electrical Box”.
Caution
Be sure to stop the
compressor before
disconnecting the refrigerant
pipe. If the refrigerant pipe is
disconnected with the
compressor running and the
stop valve opened, air may be
sucked in to generate an
over-pressure in refrigeration
cycle, thus resulting in pipe
rupture or accidental injury.
If the drain hose is
embedded in the wall,
disconnect the drain hose
beforehand.
1
Remove the screws
which fix the indoor
heat exchanger to the
installation plate.
2
Lift the indoor unit with
a wooden base.
3
Place a plastic sheet
under the drain hose as
remaining drain may
leak.
4
Disconnect the flare nut
for gas piping with 2
wrenches.
Caution
From the viewpoint of global
environmental protection,
make sure to use a vacuum
pump for air purging.
(R8014)
(R8015)
Wooden base
Drain hose
Extension drain hose
Connecting wires
(R8016)
(R8017)